INSP-Final Inspection | 3/7/2002 | 3/7/2002 | 3/7/2002 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 3/7/2002 10:16:31 AM
|
DOC - Permit Finaled | 3/7/2002 | 3/7/2002 | 3/7/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/7/2002 10:19:13 AM
|
INSP-Alarm Testing | 2/21/2002 | 2/22/2002 | 2/22/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 2/21/2002 12:42:12 PM fail; need standpipe control valve supervised; tampers on antifreeze loop not working; all dampers tested and working except exhaust dampers on 4th floor shafts; in duct detectors installed at dampers in sub basement; need copy of record of completion 2/22/2002 2:24:01 PM
|
INSP-Alarm Testing | 2/20/2002 | 2/21/2002 | 2/21/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 2/20/2002 12:16:40 PM in-duct detectors required at return air dampers in sub basement; first floor programming problems - need to retest; ground and basement alarms okay 2/21/2002 12:43:34 PM
|
INSP-Alarm Testing | 2/19/2002 | 2/20/2002 | 2/20/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 2/19/2002 4:24:35 PM smokes in bathrooms on second floor to heat detectors; some dampers not closing 2/20/2002 11:42:06 AM
|
INSP-Alarm Testing | 2/19/2002 | 2/19/2002 | 2/19/2002 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 2/19/2002 4:24:10 PM 4th floor NAC not reporting batery loss trouble; need detectors at 4th floor exhaust dampers
|
INSP-Alarm Testing | 2/15/2002 | 2/15/2002 | 2/15/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 2/15/2002 12:33:58 PM tested all sprinkler control and tampers - okay; tested 4th floor and extender panel will not report trouble with battery loss; need to test dampers on 4th; no audibles on all floors 2/15/2002 12:37:46 PM
|
FIR-Aging Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | | NR |
Rick Jackson
|
|
|
wip 2/1/2002 9:37:08 AM
|
FIR-Aging Inspection | 1/18/2002 | 1/18/2002 | 1/18/2002 | | NR |
Rick Jackson
|
|
|
wip 1/18/2002 11:59:48 AM
|
Issue permit | | | 10/19/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/16/2001 | | 10/16/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/16/2001 | | DONE |
|
|
|
permit ready
|
Telephone call | | | 10/15/2001 | | DONE |
|
|
|
reviewed FAC P battery calc procedures and size to be installed with Jim Shilton, Honeywell. He will fax Mfgr's battery requirements for the NAC extender power supply.
|
Alarm Plan Check | | | 10/15/2001 | | PASS |
|
|
|
review completed with telephone information from Honeywell.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/15/2001 | | PASS |
|
|
|
|
Plan assigned to (SAM) | 8/7/2001 | | 10/15/2001 | | DONE |
|
|
|
10/15/2001 14:35:39 SLR - activity updated through activity FIRA22 from case FIR01-00435.
|
Alarm Plan Check | | | 10/13/2001 | | PEND |
|
|
|
cannot complete review due to lack of battery details.
|
Alarm Plan Check | | | 8/31/2001 | | FAIL |
|
|
|
Review comments discussed with Randy Dinger, designer and faxed to him and Honeywell.
|
Application received | | | 8/7/2001 | | |
|
|
|
|