DOC - Permit Finaled | 12/6/2001 | 12/6/2001 | 12/6/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 12/6/2001 5:03:58 PM Fire sprinkler system finaled
|
INSP-Final Inspection | 11/30/2001 | 11/30/2001 | 11/30/2001 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinkler system finaled. OK for perm occ 11/30/2001 10:32:00 AM
|
INSP-Final Inspection | 11/7/2001 | 11/8/2001 | 11/8/2001 | A | FAIL |
Troy Cobbley
|
|
|
Change rack heads to QR, install drum drip sign, valve on in rack system to be monitored. Trip test of dry valve OK. Hydro test OK 11/8/2001 11:47:23 AM
|
Issue permit | | | 10/15/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/12/2001 | | 10/12/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/12/2001 | | DONE |
|
|
|
permit ready
|
Sprinkler Plan Check | 10/10/2001 | | 10/11/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/11/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 8/13/2001 | | 10/4/2001 | | DONE |
|
|
|
10/4/2001 14:06:15 SLR - activity updated through activity FIRA22 from case FIR01-00338.
|
Sprinkler Plan Check | 9/26/2001 | | 10/3/2001 | | FAIL |
Bill Alexander
|
|
|
2nd review did not answer many for the first review requirements. Did not meet UFC 79 and 80 for water density requirements with storage system and quantities. Will require an approved FPE verification. (UFC103.1.2)
|
Sprinkler Plan Check | 8/13/2001 | | 8/21/2001 | | FAIL |
Bill Alexander
|
|
|
Plans and system/s are not verified to meet minimum design requirements to verify protection per the UFC through minimum requirements of 1001.3, and NFPA Chapter 7.
|
Miscellaneous action | | | 8/21/2001 | | DONE |
|
|
|
Denied plans and calcs taken to the front desk for returning.
|
Telephone call | | | 8/21/2001 | | DONE |
|
|
|
Faxed copy of review to Treasure Valley Fire Protection 8:45am.
|
Telephone call | | | 8/21/2001 | | DONE |
|
|
|
denied plans.
|
Application received | | | 8/13/2001 | | |
|
|
|
|