DOC - Permit Finaled | 11/14/2001 | 11/14/2001 | 11/14/2001 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/14/2001 11:23:36 AM
|
INSP-Final Inspection | 11/9/2001 | 11/13/2001 | 11/13/2001 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled. 11/14/2001 11:23:17 AM
|
Issue permit | | | 10/25/2001 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 8/22/2001 | | 10/23/2001 | | DONE |
|
|
|
10/23/2001 09:05:31 SLR - activity updated through activity FIRA22 from case FIR01-00459.
|
Alarm Plan Check | | | 10/23/2001 | | PASS |
|
|
|
Resubmittal acceptable. RUSHED the 10/22/01resubmittal review at contractors request.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2001 | | PASS |
|
|
|
|
Inspection Record Card- Fire | 10/23/2001 | | 10/23/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/23/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Alarm Plan Check | | | 10/18/2001 | | FAIL |
|
|
|
Front desk review of resubmittal "walked in" by Troy of Mtn Alarm. Plans show HVAC DD's chagned to approved 120v, with reset/LEd's. Also added antifreeze flow switch which should be deleted, as it is not required. Revised battery calc's req. 22 AH, plans show two 12 AH batteries but FAC panel can only hold 1, 7AH battery per cut sheet. Must add aListed separate battery enclosure w/ charging power supply for the 2nd battery monitored for integrity, and verify the FACP panel can hold and charge a 12 AH instead of 7 AH battery.
|
Alarm Plan Check | | | 10/9/2001 | | FAIL |
|
|
|
Faxed revised review to Mountain Alarm. Incompatible duct detectors, lacking AF/ VT supvn and battery details.
|
Alarm Plan Check | | | 9/7/2001 | | FAIL |
|
|
|
Faxed review comments to Mountain Alarm
|
Application received | | | 8/22/2001 | | |
|
|
|
|