Permit NumberFIR01-00477
StatusFinaled
Name RICHARD HONSINGER
Site Address 911 N MOUNTAIN COVE RD
Project NameALM-MTN COVE DAY CARE
Customer Number 
ePlanReview 
Description
MTN COVE HIGH SCHOOL-DAY CARE-BLDG #8 - To provide a manual pulls, smoke and heat detectors and horn/strobes as required for the new day care occupancy in this existing relocatable building, connected to the existing school fire alarm system. The building permit (BLD01-01825) is to remodel an existing 1,917 sq. ft., single story relocatable building used as a day care per approved plans on file.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection2/1/20022/1/20022/1/2002 PASS
DetailsRick Jackson
DOC - Permit Finaled2/1/20022/1/20022/1/2002APASS
DetailsRick Jackson
Finaled by inspector at 2/1/2002 9:21:02 AM
INSP-Final Inspection12/6/200112/7/200112/7/2001PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/06/2001 at 08:13:35. Contact: .
DOC - Permit Finaled12/7/200112/7/200112/7/2001PPASS
DetailsRick Jackson
Finaled by inspector at 12/7/2001 4:29:50 PM
Miscellaneous action  10/17/2001  
letterof 10/16/2001 from architect Richard Honsinger, confirms the HVAC units are 1000 CFM each, therefore the two combined are not over 2000 CFM, therefore SD shutdown is not required.
Issue permit  10/15/2001 DONE
Telephone call  10/4/2001 DONE
Plan assigned to (SAM)9/5/2001 10/3/2001 DONE
10/3/2001 15:41:52 SLR - activity updated through activity FIRA22 from case FIR01-00477.
Alarm Plan Check  10/3/2001 PASS
Resbmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  10/3/2001 PASS
Inspection Record Card- Fire10/3/2001 10/3/2001 DONE
Alarm Plan Check  9/19/2001 FAIL
Discussed review comments with designer, Jeff Hill, Farren Engineering; they reportedly have no resposibility for the review deficiencies noted.
Application received  9/5/2001