Permit Information
Permit NumberFIR01-00488
StatusFinaled
Name AEI
Site Address 475 W PARKCENTER BLVD
Project NameALM-DOUBLE TREE HOTEL
Customer Number 
ePlanReview 
Description
NEXTEL PARTNERS / Double Tree Inn - To add a fire alarm system, including an EST LSS4 "releasing" alarm control panel, to operate a new preaction sprinkler system protecting a new roof-top cellular phone transmission building. The new releasing panel will be monitored by the new Fire Alarm Control panel which is to be installed in the Double Tree Hotel under permit number FIR02-00007. The building permit (BLD 01-01681) is for a new State approved modular building installation and antenna installation on roof of existing hotel building. Work to include installation of a 10'x20' noncombustible modular penthouse building on roof and antenna installations on roof. This is a Scope of Work Permit. Letter of Completion to be issued when done. NOTE: The building is fully fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/6/20023/6/20023/6/2002APASS
DetailsRick Jackson
Added by Inspector: 409 On 3/6/2002 7:25:21 AM
DOC - Permit Finaled3/6/20023/6/20023/6/2002PPASS
DetailsRick Jackson
Finaled by inspector at 3/6/2002 7:25:45 AM
INSP-Alarm Testing3/1/20023/4/20023/4/2002PFAIL
DetailsRick Jackson
###-#### need audible in Nextel from system alarm 3/4/2002 4:50:25 PM
INSP-Final Inspection3/1/20023/4/20023/4/2002PFAIL
DetailsRick Jackson
###-#### need audible alarm in Nextel from system alarm 3/4/2002 4:51:01 PM
Issue and Print Permit  3/1/2002 DONE
Telephone call  2/19/2002 DONE
LEFT MESS THAT PERMIT IS READY
Alarm Plan Check  2/8/2002 PASS
Plans approved after new alarm panel approved for Double Tree under Fir 02-00007.
PLANS/APPL TAKEN TO FRONT DESK  2/8/2002 DONE
Inspection Record Card- Fire2/8/2002 2/8/2002 DONE
Telephone call  2/8/2002 DONE
Alarm Plan Check  10/10/2001 FAIL
Additional details still not received from AEI. Faxed written review comments to AEI and to Double Tree Inn (Ray Horma)
Telephone call  9/26/2001 FAIL
9/26/01-Jason at AEI indicates the existing building Simplex FAC Panel does not have 60 hr batteries nor the capacity to add 60 hrs of batteries to it. He is still working on redesign of plans to connect the new releasing panel for Nextel to the building panel; they have a deadline of Friday to have it complete; thereafter penalties apply. I will work with them to get the Nextel releasing panel plans approved on RUSH basis but replacing the building panel will require a full alarm system upgrade of the Double Tree. I recommended they contact Dave Miller ASAP for an extension to upgrade the existing Double Tree building system in order for me to aprove AEI's releasing system plans for Nextel.
Alarm Plan Check  9/18/2001 FAIL
9/26-lack of information on FAC panel and improper design for connecting releasing panel to existing building panel.
Plan assigned to (SAM)9/7/2001 9/12/2001 DONE
9/12/2001 08:14:28 JWA - activity updated through activity FIRA22 from case FIR01-00468.
Application received  9/7/2001