INSP-Final Inspection | 3/6/2002 | 3/6/2002 | 3/6/2002 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 3/6/2002 7:25:21 AM
|
DOC - Permit Finaled | 3/6/2002 | 3/6/2002 | 3/6/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/6/2002 7:25:45 AM
|
INSP-Alarm Testing | 3/1/2002 | 3/4/2002 | 3/4/2002 | P | FAIL |
Rick Jackson
|
|
|
###-#### need audible in Nextel from system alarm 3/4/2002 4:50:25 PM
|
INSP-Final Inspection | 3/1/2002 | 3/4/2002 | 3/4/2002 | P | FAIL |
Rick Jackson
|
|
|
###-#### need audible alarm in Nextel from system alarm 3/4/2002 4:51:01 PM
|
Issue and Print Permit | | | 3/1/2002 | | DONE |
|
|
|
|
Telephone call | | | 2/19/2002 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Alarm Plan Check | | | 2/8/2002 | | PASS |
|
|
|
Plans approved after new alarm panel approved for Double Tree under Fir 02-00007.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/8/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/8/2002 | | 2/8/2002 | | DONE |
|
|
|
|
Telephone call | | | 2/8/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/10/2001 | | FAIL |
|
|
|
Additional details still not received from AEI. Faxed written review comments to AEI and to Double Tree Inn (Ray Horma)
|
Telephone call | | | 9/26/2001 | | FAIL |
|
|
|
9/26/01-Jason at AEI indicates the existing building Simplex FAC Panel does not have 60 hr batteries nor the capacity to add 60 hrs of batteries to it. He is still working on redesign of plans to connect the new releasing panel for Nextel to the building panel; they have a deadline of Friday to have it complete; thereafter penalties apply. I will work with them to get the Nextel releasing panel plans approved on RUSH basis but replacing the building panel will require a full alarm system upgrade of the Double Tree. I recommended they contact Dave Miller ASAP for an extension to upgrade the existing Double Tree building system in order for me to aprove AEI's releasing system plans for Nextel.
|
Alarm Plan Check | | | 9/18/2001 | | FAIL |
|
|
|
9/26-lack of information on FAC panel and improper design for connecting releasing panel to existing building panel.
|
Plan assigned to (SAM) | 9/7/2001 | | 9/12/2001 | | DONE |
|
|
|
9/12/2001 08:14:28 JWA - activity updated through activity FIRA22 from case FIR01-00468.
|
Application received | | | 9/7/2001 | | |
|
|
|
|