INSP-Final Inspection | 1/22/2003 | 1/23/2003 | 1/23/2003 | P | PASS |
Rick Jackson
|
|
|
###-####
|
DOC - Permit Finaled | 1/23/2003 | 1/23/2003 | 1/23/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/23/2003 1:41:59 PM
|
INSP-Final Inspection | 1/8/2003 | 1/8/2003 | 1/8/2003 | P | FAIL |
Rick Jackson
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie AHU on 2nd floor not shutting down on alarm; lockout on circuit breaker for FACP; map at FACP; labels on grid for concealed detectors; troubles not reporting to monitoring company; record of completion due on final 1/8/2003 3:43:33 PM
|
FIR-Aging Inspection | 12/12/2002 | 12/12/2002 | 12/19/2002 | | PART |
Rick Jackson
|
|
|
talked to Chris about this and he will get the final inspection scheduled 12/19/2002 10:39:04 AM
|
Issue permit | | | 11/5/2001 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 9/10/2001 | | 9/25/2001 | | DONE |
|
|
|
9/25/2001 09:15:25 SLR - activity updated through activity FIRA22 from case FIR01-00491.
|
Alarm Plan Check | | | 9/25/2001 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/25/2001 | | PASS |
|
|
|
|
Inspection Record Card- Fire | 9/25/2001 | | 9/25/2001 | | DONE |
|
|
|
|
Telephone call | | | 9/25/2001 | | DONE |
|
|
|
|
Application received | | | 9/10/2001 | | |
|
|
|
|