Permit Information
Permit NumberFIR01-00495
StatusFinaled
Name ST LUKES REG
Site Address 190 E BANNOCK ST
Project NameST LUKES-CENTRAL WING
Customer Number 
ePlanReview 
Description
SLRMC CENTRAL WING, GROUND & FIRST FLOOR- DIETARY EXHAUST HOOD REMODEL - To provide fire alarm monitoring of the relocated DIETARY kitchen exhaust hood extinguishing system, to be connected to the existing fire alarm system. The building permit (BLD01-00495) is to remove and relocate the existing grease duct exhaust & reinstall per plan to provide room for new Type I hood & duct system. To relocate and modify existing utilities & HVAC ducts as necessary to install the new and relocated grease exhaust ducts & provide room for installation of the "FireMaster" Duct Wrap - per ER#4975 - 2 layers of 2" nominal thickness and 7 pcf, as the two-hour shaft. To reinstall / relocate the utilities & ducts previously removed; install the sprinkler system hood protection & fire protection around the hoods as necessary to meet sections 1003 & 1006, 1997 UFC; and sections 506 thru 509, Chapter 6 & 12, 1997 UMC; and Chapter 7 & Section 904, 1997 UBC. A "Letter of Completion / Compliance" is required for final approval of this project scope.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/11/20024/11/20024/11/2002PPASS
DetailsRick Jackson
Scheduled by Inspector: 409 On 4/11/2002 11:14:26 AM
DOC - Permit Finaled4/11/20024/11/20024/11/2002PPASS
DetailsRick Jackson
Finaled by inspector at 4/11/2002 4:23:01 PM
INSP-Final Inspection4/10/20024/10/20024/10/2002PNR
DetailsRick Jackson
Scheduled by Inspector: 409 On 4/10/2002 2:42:43 PM
INSP-Final Inspection3/13/20023/14/20023/14/2002AFAIL
DetailsRick Jackson
###-#### MARK electrical under hood didn't shut off with system activation; need to access the shaft and wrap 3/14/2002 12:30:17 PM
FIR-Aging Inspection2/1/20022/1/20022/1/2002 NR
DetailsRick Jackson
wip 2/1/2002 9:54:53 AM
FIR-Aging Inspection12/25/200112/25/200112/26/2001 NR
DetailsRick Jackson
wip 12/26/2001 6:49:56 AM
Inspection Record Card- Fire9/25/2001 9/25/2001 DONE
Telephone call  9/25/2001 DONE
Issue and Print Permit  9/25/2001 DONE
Plan assigned to (SAM)9/11/2001 9/24/2001 DONE
9/24/2001 13:31:01 SLR - activity updated through activity FIRA22 from case FIR01-00495.
Alarm Plan Check  9/24/2001 PASS
PLANS/APPL TAKEN TO FRONT DESK  9/24/2001 PASS
Application received  9/11/2001