(F) Reprint permit | | | 4/24/2002 | | DONE |
|
|
|
|
INSP-Final Inspection | 12/3/2001 | 12/4/2001 | 12/4/2001 | P | FAIL |
Troy Cobbley
|
|
|
End sprinkler heads along the north and south walls are more than 3-11 1/2 from wall, max. storage height is exceeded through-out store, provide flow switch and check valve on the hose rack system, provide the required spare heads in cabinet, provide draft stops, provide heat and smoke removal vents, hose racks in warehouse are not accessible, hydro test system, provide "fire sprinkler riser" sign on door accessing riser, provide sign on exterior alarm bell, provide "no parking-fire lane" on north exterior wall, remove dumpster to provide clearance for fire dept access, provide verification on duct detectors for store, provide rack information to Boise City for verification of requirements (racks are solid shelves which is not per agreement). Inspection is not complete. I will return by the following day to complete. 12/4/2001 4:48:30 PM
|
Issue and Print Permit | | | 12/3/2001 | | DONE |
|
|
|
|
Issue permit | | | 12/3/2001 | | DONE |
|
|
|
|
Issue permit | | | 12/3/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/30/2001 | | 11/30/2001 | | DONE |
|
|
|
|
Telephone call | | | 11/30/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/27/2001 | | 11/30/2001 | | PASS |
Bill Alexander
|
|
|
Sprinklers approved on conditions (refer to review notes and field verification). Building issues not verified by plans meeting Article 81.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/30/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 11/16/2001 | | 11/19/2001 | | FAIL |
Bill Alexander
|
|
|
Calculations do not have the required 5% cushion per the State FM requirement.
|
Sprinkler Plan Check | 9/24/2001 | | 11/19/2001 | | PART |
Bill Alexander
|
|
|
PARTIAL - Proceed at contractors risk. Requires reverficiation of water supply certification and recalculations with a correct K-factor head (using current water supply information).
Updated 11/19/2001 - Calculations are lacking cushion.
|
Sprinkler Plan Check | 11/1/2001 | | 11/14/2001 | | FAIL |
Bill Alexander
|
|
|
Fire Hose Station Layout and building plans lack detail to verify UFC 8101.3.2, 8102.8, 1001.3. Calculations are still difficient!
|
Telephone call | | | 11/14/2001 | | DONE |
|
|
|
Left message that permit needs to be picked up & review last review failed!
|
Inspection Record Card- Fire | 9/27/2001 | | 9/27/2001 | | DONE |
|
|
|
|
Telephone call | | | 9/27/2001 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/27/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/26/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 9/12/2001 | | 9/26/2001 | | DONE |
|
|
|
9/26/2001 16:18:51 JWA - activity updated through activity FIRA22 from case FIR01-00498.
|
Sprinkler Plan Check | 9/13/2001 | | 9/24/2001 | | FAIL |
Bill Alexander
|
|
|
Lack verification of "Most Remote". Lack current water supply information. Lack full fitting and riser length input. Lack 5% minimum pressure cushion.
|
Telephone call | | | 9/24/2001 | | DONE |
|
|
|
Called John Warnick and requested additional information. 3:00pm
|
Application received | | | 9/12/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|