Permit NumberFIR01-00499
StatusFinaled
Name PROTEX
Site Address 104 N MILWAUKEE
Project NameALM-BOISE THEATER/RETAIL SHOPS
Customer Number 
ePlanReview 
Description
Boise Theater/Retail Shops - To replace an existing fire alarm panel with a new system. The new system will monitor the fire sprinkler systems and the HVAC duct detectors for air handler monitoring. No building permit is associated with this project.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing3/22/20023/25/20023/25/2002APASS
DetailsTroy Cobbley
fire alarm system finaled 3/25/2002 11:03:58 AM
DOC - Permit Finaled3/25/20023/25/20023/25/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 3/25/2002 11:04:05 AM
INSP-Final Inspection3/6/20023/8/20023/8/2002ACANC
DetailsTroy Cobbley
cancelled by the contractor 3/8/2002 10:40:39 AM
Alarm Plan Check2/12/2002 2/12/2002 PASS
Approved revised plans to add monitoring of kitchen hood system and additional HVAC units.
FIR-Aging Inspection2/1/20022/1/20022/1/2002 NR
DetailsTroy Cobbley
work in progress 2/1/2002 11:51:57 AM
INSP-Final Inspection1/17/20021/18/20021/18/2002AFAIL
DetailsTroy Cobbley
Contractor needs to resubmit showing substitution of spot detectors for duct detectors in "Mens Warehouse", HVAC unit in "Billiards and BarStools" does not shut down, provide map of device locations and addresses at the FACP 1/18/2002 11:48:31 AM
INSP-Conference12/3/200112/3/200112/3/2001PDONE
DetailsTroy Cobbley
Contractor wanted alternate location for remote annunciator. I referred it to Sam Rogers 12/4/2001 11:28:48 AM
Inspection Record Card- Fire10/11/2001 10/11/2001 DONE
Telephone call  10/11/2001 DONE
left mess that permit is ready
Issue permit  10/11/2001 DONE
Plan assigned to (SAM)9/12/2001 10/10/2001 DONE
10/10/2001 16:05:43 SLR - activity updated through activity FIRA22 from case FIR01-00499.
Alarm Plan Check  10/10/2001 PASS
resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  10/10/2001 PASS
Alarm Plan Check  9/27/2001 PEND
Need to add relay for duct detector circuit. Discussed with Rob at Protex. He will fax cut sheet a on relay and revise battery calc's & size if 60-hr current draw exceeds 2.0AH
Application received  9/12/2001