INSP-Alarm Testing | 3/22/2002 | 3/25/2002 | 3/25/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 3/25/2002 11:03:58 AM
|
DOC - Permit Finaled | 3/25/2002 | 3/25/2002 | 3/25/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/25/2002 11:04:05 AM
|
INSP-Final Inspection | 3/6/2002 | 3/8/2002 | 3/8/2002 | A | CANC |
Troy Cobbley
|
|
|
cancelled by the contractor 3/8/2002 10:40:39 AM
|
Alarm Plan Check | 2/12/2002 | | 2/12/2002 | | PASS |
|
|
|
Approved revised plans to add monitoring of kitchen hood system and additional HVAC units.
|
FIR-Aging Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | | NR |
Troy Cobbley
|
|
|
work in progress 2/1/2002 11:51:57 AM
|
INSP-Final Inspection | 1/17/2002 | 1/18/2002 | 1/18/2002 | A | FAIL |
Troy Cobbley
|
|
|
Contractor needs to resubmit showing substitution of spot detectors for duct detectors in "Mens Warehouse", HVAC unit in "Billiards and BarStools" does not shut down, provide map of device locations and addresses at the FACP 1/18/2002 11:48:31 AM
|
INSP-Conference | 12/3/2001 | 12/3/2001 | 12/3/2001 | P | DONE |
Troy Cobbley
|
|
|
Contractor wanted alternate location for remote annunciator. I referred it to Sam Rogers 12/4/2001 11:28:48 AM
|
Inspection Record Card- Fire | 10/11/2001 | | 10/11/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/11/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 10/11/2001 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 9/12/2001 | | 10/10/2001 | | DONE |
|
|
|
10/10/2001 16:05:43 SLR - activity updated through activity FIRA22 from case FIR01-00499.
|
Alarm Plan Check | | | 10/10/2001 | | PASS |
|
|
|
resubmittal acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/10/2001 | | PASS |
|
|
|
|
Alarm Plan Check | | | 9/27/2001 | | PEND |
|
|
|
Need to add relay for duct detector circuit. Discussed with Rob at Protex. He will fax cut sheet a on relay and revise battery calc's & size if 60-hr current draw exceeds 2.0AH
|
Application received | | | 9/12/2001 | | |
|
|
|
|