DOC - Permit Finaled | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/14/2001 3:24:16 PM
|
INSP-Final Inspection | 11/14/2001 | 11/14/2001 | 11/14/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/14/2001 3:24:09 PM Fire sprinkler system finaled. OK for perm occ
|
INSP-Final Inspection | 11/1/2001 | 11/1/2001 | 11/1/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/1/2001 11:08:25 AM
|
DOC - Permit Finaled | 11/1/2001 | 11/1/2001 | 11/1/2001 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/1/2001 11:08:32 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/30/2001 | 10/30/2001 | P | PASS |
Troy Cobbley
|
|
|
Left correction notice. Install hose station outlet, pendents overspace in corr. 110, pendents not installed in restroom and computer room, taped heads in restroom, hangers missing, FDC leaking, install alarm bell, verify test orfice matches head, provide letter stating heads are installed in canopies. 10/31/2001 9:19:52 AM
|
Inspection Record Card- Fire | 10/23/2001 | | 10/23/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/23/2001 | | DONE |
|
|
|
|
Issue permit | | | 10/23/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/22/2001 | | 10/23/2001 | | PASS |
Bill Alexander
|
|
|
CANOPY SPRINKLER COVERAGE FOR COMPLETION OF HANGING RESUBMITTALS.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 10/22/2001 | | DONE |
|
|
|
|
Issue permit | | | 10/22/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/16/2001 | | 10/19/2001 | | PART |
Bill Alexander
|
|
|
Requires further verification and resumittal on outside canopies.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/19/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 10/19/2001 | | DONE |
|
|
|
Faxed copy of review to Grinnell
|
INSP-Sprinkler Rough-in/Hydro | 10/11/2001 | 10/12/2001 | 10/12/2001 | A | PART |
Troy Cobbley
|
|
|
Above ground hydro OK. No approved plans for roughin inspection 10/12/2001 2:43:57 PM
|
Issue permit | | | 10/9/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/28/2001 | | 9/28/2001 | | DONE |
|
|
|
|
Telephone call | | | 9/28/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/17/2001 | | 9/28/2001 | | DONE |
|
|
|
9/28/2001 10:36:11 JWA - activity updated through activity FIRA22 from case FIR01-00505.
|
Sprinkler Plan Check | 9/17/2001 | | 9/28/2001 | | PART |
Bill Alexander
|
|
|
CONDITIONS: Requires resubmittals of key problems and verification (reference review conditions).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/28/2001 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 9/17/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|