INSP-Final Inspection | 4/9/2003 | 4/9/2003 | 4/9/2003 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 4/9/2003 | 4/9/2003 | 4/9/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 4/9/2003 1:45:20 PM
|
INSP-Alarm Testing | 3/26/2003 | 3/31/2003 | 3/31/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/26/2003 at 11:47:48 AM. Contact: ###-####. need map at annunciator; sign on basement door; define zones for monitoring company; need record of completion 3/31/2003 4:16:01 PM
|
Telephone call | | | 3/14/2003 | | DONE |
|
|
|
telcon from Earl regarding status of this permit. He says system was installed almost a year ago but owner wouldn't allow them to call for an inspection; the elevator work has been completed and they will call for an inspection now because he says Jim Storey has issued a Warning Notice to the owner to get the permit finaled or face a power shut off.
|
FIR-Aging Inspection | 12/18/2002 | 12/18/2002 | 12/18/2002 | | PART |
Rick Jackson
|
|
|
called Earl and he said the elevator company needs to program the elevator for capture; he is going to call the elevator company 12/19/2002 10:37:59 AM
|
CHANGE STATUS TO (ISS) | | | 4/29/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/5/2001 | | 11/5/2001 | | DONE |
|
|
|
|
Telephone call | | | 11/5/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 11/5/2001 | | DONE |
|
|
|
|
Alarm Plan Check | 11/2/2001 | | 11/2/2001 | | PASS |
|
|
|
Resubmittal approved with CONDITIONS.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2001 | | PASS |
|
|
|
|
Plan assigned to (SAM) | 9/18/2001 | | 11/2/2001 | | DONE |
|
|
|
11/2/2001 17:18:59 SLR - activity updated through activity FIRA22 from case FIR01-00509.
|
Alarm Plan Check | | | 10/18/2001 | | FAIL |
|
|
|
Plans resubmitted with new address of 2404, and per the application should not be attached to any existing permit, although it appears that an electrical permit would be required for the elevator control system modifications.
alarm plans denied for several major deficiencies.
|
Alarm Plan Check | | | 9/28/2001 | | FAIL |
|
|
|
Per telcon 9/28/01 with Earl Lasater, Fire Sentry, this may be attached to the wrong permit. The FA application address does not match the BLD permit project address. This project involves replacing the existing FAC panel, which requires a full review of the building alarm requirements and upgrade to meet current code. Earl to verify address/permit number with contractor resubmit a correctly completed application, and building plans showing all necessary alarm devices. No written review done.
|
Application received | | | 9/18/2001 | | |
|
|
|
|