INSP-Final Inspection | 5/10/2002 | 5/10/2002 | 5/10/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 5/10/2002 4:26:17 PM
|
DOC - Permit Finaled | 5/10/2002 | 5/10/2002 | 5/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/10/2002 4:27:42 PM
|
INSP-Final Inspection | 5/2/2002 | 5/3/2002 | 5/3/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### call first need Bill to review clacs; wrong temp heads in garage; caps on standpipes; signs on riser room; 5/3/2002 4:35:47 PM
|
INSP-Final Inspection | 5/1/2002 | 5/2/2002 | 5/2/2002 | A | CANC |
Rick Jackson
|
|
|
fire fn- bruce ###-#### Darrell of Tytan scheduled for alarm testing on 5/3 5/2/2002 2:17:37 PM
|
INSP-Final Inspection | 4/29/2002 | 4/30/2002 | 4/30/2002 | A | CANC |
Troy Cobbley
|
|
|
Bruce called and said that the fire alarm was not ready 4/30/2002 2:21:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/19/2002 | 4/22/2002 | 4/22/2002 | A | PART |
Rick Jackson
|
|
|
r/i bruce ###-#### hydro okay for standpipe 4/22/2002 12:27:13 PM
|
Override - Parcel Holds | | | 4/19/2002 | | |
|
|
|
|
INSP-Supply line flush | 3/20/2002 | 3/21/2002 | 3/21/2002 | A | PART |
Rick Jackson
|
|
|
bruce-- ###-#### underground flush only 3/21/2002 9:58:24 AM
|
Override - Parcel Holds | | | 3/20/2002 | | |
|
|
|
|
INSP-Final Inspection | 2/13/2002 | 2/14/2002 | 2/14/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### not a final inspection; hydro okay on overhead 2/14/2002 11:07:57 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/14/2002 | 2/14/2002 | 2/14/2002 | A | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 2/14/2002 11:08:25 AM hydro on overhead okay
|
Override - Parcel Holds | | | 2/13/2002 | | |
|
|
|
|
FIR-Aging Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | | NR |
Rick Jackson
|
|
|
wip 2/1/2002 9:53:55 AM
|
Override - Parcel Holds | | | 12/28/2001 | | |
|
|
|
|
Issue and Print Permit | | | 12/28/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/27/2001 | | 12/27/2001 | | DONE |
|
|
|
|
Telephone call | | | 12/27/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 12/20/2001 | | 12/27/2001 | | PASS |
Bill Alexander
|
|
|
Resubmittal of required information for standpipes.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/27/2001 | | DONE |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in | 12/12/2001 | 12/13/2001 | 12/14/2001 | A | FAIL |
Rick Jackson
|
|
|
###-#### c/n issued: standpipe submittals required; 3/4 inch lines used to feed under stairs on third floor require calc's; 4 inch main in basement needed per calcs 12/14/2001 11:11:41 AM
|
Override - Parcel Holds | | | 12/12/2001 | | |
|
|
|
|
Issue permit | | | 10/12/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/9/2001 | | 10/9/2001 | | DONE |
|
|
|
|
Telephone call | | | 10/9/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/19/2001 | | 10/8/2001 | | DONE |
|
|
|
10/8/2001 13:29:12 JWA - activity updated through activity FIRA22 from case FIR01-00510.
|
Sprinkler Plan Check | 10/2/2001 | | 10/8/2001 | | PASS |
Bill Alexander
|
|
|
PARTIAL-STANDPIPES NEEDS RESUBMITTAL
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/8/2001 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 9/19/2001 | | 9/27/2001 | | FAIL |
|
|
|
Lack standpipe system, calculation errors, plans corelating, etc.
|
Telephone call | | | 9/27/2001 | | DONE |
|
|
|
Faxed failed review to Commercial at 11:00am.
|
Application received | | | 9/19/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|