Permit Information
Permit NumberFIR01-00512
StatusFinaled
Name ALARMCO
Site Address 5955 W CASTLE DR
Project NameALM-SUMMERWIND RETIREMENT CENT
Customer Number 
ePlanReview 
Description
Summerwind Retirement Center - To install a replacement FA control panel and upgrade the existing system to meet current code. The new panel will be a Radionics D9124 addressable point system. System coverage will include manual pull stations at all exits, partial area smoke and heat detection, fire sprinkler waterflow and valve tamper monitoring, magnetic door hold-opens powered and released by the alarm system, two duct detectors (for unidentified purpose), and full a/v annunciation.
No building permit applies to this alarm permit.
NOTE: This permit does not include the new addition. The application indicates a separate Fire Alarm Permit will be applied for, in conjunction with the building addition permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled3/8/20023/8/20023/8/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 3/8/2002 8:38:34 AM
INSP-Final Inspection3/8/20023/8/20023/8/2002APASS
DetailsTroy Cobbley
Added by Inspector: 430 On 3/8/2002 8:38:28 AM corrections completed. Fire alarm system finaled
INSP-Final Inspection2/14/20022/19/20022/19/2002AFAIL
DetailsTroy Cobbley
Contractor to verify batteries are correctly sized in NAC panels (current draw exceeded plans), NAC panels not reporting loss of AC, NAC panel AC is not hardwired (verify requirement) 2/19/2002 1:26:25 PM
Override - Parcel Holds  2/14/2002  
INSP-Final Inspection1/31/20022/4/20022/4/2002AFAIL
DetailsTroy Cobbley
relocate manual pull stations per note #12, test all fire sprinkler riser devices, provide a strobe in restroom 54, provide sign on FACP room door, provide review note #7 voltage measurements with inspector, inspection stopped at this point and will be continued. 2/4/2002 3:04:00 PM
Override - Parcel Holds  1/31/2002 DONE
DetailsAnnett Moore
Parcel Tag Notes: Do not issue any building permit until a one-lot subdivision has been recorded for this parcel. Contact Brandi Christon or Karen Gallagher for information. 11/02/01 Reason for OverRide:
Inspection Record Card- Fire12/27/2001 12/27/2001 DONE
Telephone call  12/27/2001 DONE
left mess that permit is ready
Issue permit  12/27/2001 DONE
Alarm Plan Check12/19/2001 12/26/2001 PASS
Plans approved with Conditions based on 12/18/2001 telcon with Mike at Alarmco and faxed revisions received 12/19/2001.
PLANS/APPL TAKEN TO FRONT DESK  12/26/2001 PASS
Plan assigned to (SAM)9/19/2001 12/26/2001 DONE
12/26/2001 16:32:49 SLR - activity updated through activity FIRA22 from case FIR01-00512.
Alarm Plan Check12/7/2001 12/18/2001 FAIL
Incomplete/conflicting information discussed with Mike at Alarmco. Hold for fax of necessary revisions.
Alarm Plan Check  10/5/2001 FAIL
Application incomplete, scope of work not properly defined, plans incomplete. Discussed necessary revisions with Al Mannor, Alarmco. Resubmittal required. Faxed written review 10/8 to Alarmco (incorrect fax number on application).
Application received  9/19/2001