INSP-Final Inspection | 5/2/2002 | 5/2/2002 | 5/2/2002 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 5/2/2002 2:45:03 PM
|
DOC - Permit Finaled | 5/2/2002 | 5/2/2002 | 5/2/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/2/2002 2:45:11 PM
|
INSP-Final Inspection | 5/1/2002 | 5/1/2002 | 5/1/2002 | P | FAIL |
Troy Cobbley
|
|
|
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer
|
INSP-Final Inspection | 3/20/2002 | 3/21/2002 | 3/21/2002 | A | FAIL |
Rick Jackson
|
|
|
JIM ###-#### FOR ACCESS exposed CPVC in riser/mechanical room. GC will get with TVFP and provide clarification; appears not to meet listing of Blazemaster 3/21/2002 9:14:13 AM
|
INSP-Sprinkler Rough-in | 11/14/2001 | 11/15/2001 | 11/15/2001 | A | PASS |
Troy Cobbley
|
|
|
OK for cover up 11/15/2001 2:21:25 PM
|
Override - Parcel Holds | | | 11/14/2001 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 10/22/2001 | 10/22/2001 | 10/22/2001 | P | PASS |
Troy Cobbley
|
|
|
Rough-in OK. Tenting inspec. needs to be done. Install head beneath stairs. 10/24/2001 8:24:51 AM
|
Override - Parcel Holds | | | 10/22/2001 | | |
|
|
|
|
Issue permit | | | 10/2/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/1/2001 | | 10/1/2001 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 9/21/2001 | | 10/1/2001 | | DONE |
|
|
|
10/1/2001 13:26:34 JWA - activity updated through activity FIRA22 from case FIR01-00514.
|
Sprinkler Plan Check | 9/21/2001 | | 10/1/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/1/2001 | | DONE |
Bill Alexander
|
|
|
|
Application received | | | 9/21/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|