INSP-Sprinkler Rough-in/Hydro | 11/21/2001 | 11/26/2001 | 11/26/2001 | A | FAIL |
Troy Cobbley
|
|
|
provide sign on valve, connect tamper switch, caulk pipe penatrations, place bags on pendents, pressure test system, place hydraulic sticker, provide access door on vent piping 11/26/2001 8:33:20 AM
|
INSP-Final Inspection | 11/26/2001 | 11/26/2001 | 11/26/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/26/2001 4:04:50 PM Problems corrected. Fire sprinkler system finaled.
|
DOC - Permit Finaled | 11/26/2001 | 11/26/2001 | 11/26/2001 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 11/26/2001 4:04:57 PM
|
Issue and Print Permit | | | 11/20/2001 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/19/2001 | | 11/19/2001 | | DONE |
|
|
|
|
Telephone call | | | 11/19/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 11/15/2001 | | 11/19/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/19/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 10/31/2001 | | 11/15/2001 | | DONE |
|
|
|
11/15/2001 10:08:31 JWA - activity updated through activity FIRA22 from case FIR01-00586.
|
Sprinkler Plan Check | 10/31/2001 | | 11/9/2001 | | FAIL |
Bill Alexander
|
|
|
|
Telephone call | | | 11/9/2001 | | DONE |
Bill Alexander
|
|
|
Faxed copy of failed review to Shilo 11:30am. (Fax: ###-####)
|
Application received | | | 10/31/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|