Case Summary | | | 2/26/2015 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 | P | PASS |
Rick Jackson
|
|
|
updating record to reflect this is completed
|
DOC - Permit Finaled | 6/27/2003 | 6/27/2003 | 6/27/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/27/2003 12:34:16 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2002 | 7/24/2002 | 7/24/2002 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/23/2002 at 11:40:05. Contact: ###-####. hydro okay; will need alarm plans for new tamper; heads obstructed by lights; 4 ft wide obstruction requires head underneath it; pressure switch on dry valve needs supervised switch 7/24/2002 10:41:10 AM
|
Issue permit | | | 5/31/2002 | | |
|
|
|
|
Sprinkler Plan Check | 5/23/2002 | | 5/29/2002 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/29/2002 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/29/2002 | | 5/29/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/29/2002 | | DONE |
|
|
|
left message permit ready and fees due
|
Issue permit | | | 5/9/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/7/2002 | | 5/7/2002 | | PART |
Bill Alexander
|
|
|
Existing 6" D.I. underground piped under a concrete floor approximately 1"-7 in and 8'-0" over to riser location. (Response asking for allowance)
|
Telephone call | | | 5/7/2002 | | DONE |
|
|
|
Called Rick Reynolds (got his voice mail). Asked if this was a resubmittal or something for Dave to look at? If sprinkler resubmittal; need permit appliction attached and marked as resubmittal.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/7/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 11/8/2001 | | 5/7/2002 | | DONE |
|
|
|
5/7/2002 16:31:46 JWA - activity updated through activity FIRA22 from case FIR01-00582.
|
Telephone call | | | 2/19/2002 | | DONE |
|
|
|
BRYAN PICKED UP NO FEE///DLD
|
Telephone call | | | 11/16/2001 | | DONE |
|
|
|
permit ready
|
Sprinkler Plan Check | 11/8/2001 | | 11/15/2001 | | FAIL |
Bill Alexander
|
|
|
Lack full coverage and correct calculations. Require seperate controls. Need water certification. Need waiver from F.D. allowance for existing underground location built over, now a cover facility. Need added data submittals, coversheets, etc.
|
Application received | | | 11/8/2001 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|