(F) Reprint permit | | | 2/7/2007 | | |
|
|
|
|
INSP-Final Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | A | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 2/1/2002 10:19:11 AM Fire alarm system finaled
|
DOC - Permit Finaled | 2/1/2002 | 2/1/2002 | 2/1/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 2/1/2002 10:19:17 AM
|
INSP-Final Inspection | 1/28/2002 | 1/29/2002 | 1/29/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide one additional duct detector on unit in Koppels, provide knox box with map inside, provide sign on fire sprinkler riser door, provide locks on breakers for FACP and electric alarm bell 1/30/2002 9:59:10 AM
|
Issue permit | | | 1/14/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 11/15/2001 | | 1/11/2002 | | DONE |
|
|
|
1/11/2002 13:04:17 SLR - activity updated through activity FIRA22 from case FIR01-00594.
|
Alarm Plan Check | 1/9/2002 | | 1/11/2002 | | PASS |
|
|
|
Resubmittal acceptable with delayed upgrade agreement approved by the FD
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/11/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/11/2002 | | 1/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2002 | | DONE |
|
|
|
DAVE ###-####
|
Alarm Plan Check | | | 11/27/2001 | | FAIL |
|
|
|
Plans are to replace the FAC panel; must include the entire building; plans are only for TI area. Phoned ADT, Phil Omas, and discussed info required for resubmittal
|
Application received | | | 11/15/2001 | | |
|
|
|
|