INSP-Final Inspection | 9/2/2003 | 9/3/2003 | 9/3/2003 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/2/2003 at 10:12:21 AM. Contact: ###-####.
|
DOC - Permit Finaled | 9/3/2003 | 9/3/2003 | 9/3/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 9/3/2003 2:45:13 PM
|
INSP-Final Inspection | 2/18/2003 | 2/21/2003 | 2/21/2003 | A | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need updated map with initiating devices as plans at job site were not clear; need supervised ball valves on dry system alarm switches; verify NAC's as not installed per plans; FBI area tested okay - no need to retest this area; need tampers to report supervisory and not trouble; retest intiating devices in basement; need notification device in workroom 2/21/2003 3:19:42 PM
|
INSP-Conference | 8/16/2002 | 8/20/2002 | 8/20/2002 | P | CANC |
Rick Jackson
|
|
|
###-#### JEREMY canceled by Chris of Simplex 8/21/2002 8:09:32 AM
|
Issue permit | | | 1/31/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/30/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/30/2002 | | 1/30/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/30/2002 | | DONE |
|
|
|
SPOKE WITH STEPHANIE PLANS READY
|
Plan assigned to (SAM) | 11/26/2001 | | 1/30/2002 | | DONE |
|
|
|
1/30/2002 08:58:17 SLR - activity updated through activity FIRA22 from case FIR01-00596.
|
Alarm Plan Check | 12/24/2001 | | 1/4/2002 | | FAIL |
|
|
|
Resubmittal not complete. Meeting held 1/3/02 with Stephanie Cribbs of Simplex to discuss revisions needed. Will resubmit.
|
Alarm Plan Check | | | 12/3/2001 | | FAIL |
|
|
|
Review cannot be completed; plans are a modification of previoulsy approved plans and are incomplete. Phoned Simplex and discussed issues with Stephanie and Peter Petroni.
|
Application received | | | 11/26/2001 | | |
|
|
|
|
Alarm Plan Check | | | 1/29/2001 | | PASS |
|
|
|
resubmittal approved with conditions
|