INSP-Final Inspection | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler finaled
|
DOC - Permit Finaled | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 9/12/2002 2:27:03 PM
|
INSP-Final Inspection | 7/23/2002 | 7/24/2002 | 7/24/2002 | P | CANC |
Troy Cobbley
|
|
|
contractor called and said that the correct orfice is installed in the inspectors test. 7/24/2002 2:51:11 PM
|
INSP-Sprinkler Rough-in/Hydro | 2/19/2002 | 2/22/2002 | 2/22/2002 | P | PART |
Troy Cobbley
|
|
|
hydro test for canopy anti-freeze system OK 2/22/2002 5:05:07 PM
|
Issue permit | | | 2/4/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/29/2002 | | 1/30/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/30/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 1/30/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/27/2001 | | 1/30/2002 | | DONE |
Bill Alexander
|
|
|
1/30/2002 14:49:15 JWA - activity updated through activity FIRA22 from case FIR01-00602.
|
Telephone call | | | 1/24/2002 | | DONE |
Bill Alexander
|
|
|
Received a telephone call from Dant'e (Grinnell) requesting what the problem is with the submittal. Looked at shelved plans an calcs and reiterated pretty much the same problems as previously requrested. Plans and calculations to correlate!
|
Sprinkler Plan Check | 12/17/2001 | | 12/20/2001 | | FAIL |
Bill Alexander
|
|
|
Lack a full set of calculations on the issues of the first review (this permit).
|
Telephone call | | | 12/20/2001 | | DONE |
|
|
|
Faxed copy of required information (full set of calcs) to finish review to Grinnell/Tom Easton.
|
Inspection Record Card- Fire | 12/5/2001 | | 12/5/2001 | | DONE |
|
|
|
|
Telephone call | | | 11/30/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 11/29/2001 | | |
|
|
|
|
Sprinkler Plan Check | 11/27/2001 | | 11/29/2001 | | PART |
Bill Alexander
|
|
|
Calculations and plans do not correlate. Remote area "Canopy" not designed to calculated density/area spacing. Plan submittal/modifications not accepted
|
Miscellaneous action | | | 11/29/2001 | | DONE |
Bill Alexander
|
|
|
Took denied plans to front desk for calling and return.
|