Permit Information
Permit NumberFIR01-00625
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 11311 W CHINDEN BLVD
Project NameALM-HEWLETT-PACKARD BLDG 4
Customer Number 
ePlanReview 
Description
HEWLETT-PACKARD Bldg 4 - This permit is limited to the lower and upper floors of Building 4. The "middle" floor was reportedly upgraded as part of a TI project approximately 3 years ago and is not included in this permit. This permit is to modify the initiation circuits and provide new notification appliances on the "lower" and "upper" levels to meet current code. A new NAC panel is to be installed to power the notification devices on the "upper" level. There is no building permit associated with this fire alarm work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection10/21/200510/21/200510/23/2005 PASS
DetailsTroy Cobbley
INSP-Final Inspection10/23/200510/23/200510/23/2005PPASS
DetailsTroy Cobbley
Inspection finaled 10/21/05
INSP-Final Inspection10/21/200510/21/200510/21/2005PPASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection8/17/20058/17/20058/17/2005 PASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection6/14/20056/14/20056/15/2005 DONE
DetailsTroy Cobbley
I left message on Brad Turks voice mail requesting the status of this job.
INSP-Final Inspection8/2/20028/6/20028/6/2002ACANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 08/02/2002 at 08:34:54. Contact: .
inspection not done due to no contact number being given. With the site being HP I can't get beyond the security office without a chaperone. 8/6/2002 4:28:13 PM
Miscellaneous action  4/29/2002 DONE
4 hrs of inspections done after hour at 42.00 for each hour.
INSP-Alarm Testing4/22/20024/25/20024/25/2002PFAIL
DetailsTroy Cobbley
provide ceiling listed horn/strobe, relocate heat detector to within 2' of sprinkler head on first floor and adjust all fire doors so that they latch 4/26/2002 7:21:15 AM
Inspection Record Card- Fire1/11/2002 1/11/2002 DONE
Telephone call  1/11/2002 DONE
left mess that permit is ready
Issue permit  1/11/2002 DONE
Alarm Plan Check  1/10/2002 PASS
PLANS/APPL TAKEN TO FRONT DESK  1/10/2002 DONE
Plan assigned to (SAM)12/20/2001 1/10/2002 DONE
1/10/2002 19:35:10 SLR - activity updated through activity FIRA22 from case FIR01-00625.
Telephone call  1/7/2002 DONE
telcon with Bran Graham indicated "middle level" not in this project and was upgraded 3 years ago under a City permit. No work is to be done on "middle level". The submitted circuit diagram and calcualtions Sheet 1) do include the middle level. Agreed this permit will be issued with the 2nd floor excluded.
Alarm Plan Check  1/4/2002 PEND
inadequate information regarding the middle level of building. Called simplex who doesn not have information; they suggest holding for clarification from HP.
Left message for John Hatton at HP.
Alarm Plan Check12/20/2001 12/27/2001 HOLD
Need additional information. Called HP and Simlex, no one available until next week. Hold for further information.
Application received  12/20/2001