INSP-Final Inspection | 6/17/2003 | 6/17/2003 | 6/17/2003 | P | PASS |
Rick Jackson
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore panel was clear and Jim Thresher said the remote annunciator and a board had to changed to fix the ground fault 6/17/2003 3:35:39 PM
|
DOC - Permit Finaled | 6/17/2003 | 6/17/2003 | 6/17/2003 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/17/2003 3:35:43 PM
|
INSP-Final Inspection | 5/27/2003 | 6/3/2003 | 6/3/2003 | A | FAIL |
Rick Jackson
|
|
|
JIM - THRESHER - CELL ###-####-- need sign on fifth floor door for control valves; FACP has earth ground fault and will need to be cleared for final (new mother board coming on Thursday from Simplex) 6/3/2003 2:47:22 PM
|
Issue permit | | | 5/27/2003 | | |
|
|
|
|
(F) Reprint permit | | | 5/27/2003 | | |
|
|
|
|
INSP-Conference | 4/15/2003 | 4/15/2003 | 4/15/2003 | P | DONE |
Rick Jackson
|
|
|
met with Jim Thrasher and told him that he has 30 days to get the scope of this permit completed and tested; told him again that the permit is ready for pick up at the permit desk
|
INSP-Conference | 4/2/2003 | 4/2/2003 | 4/2/2003 | A | PART |
Rick Jackson
|
|
|
met with Jim thrasher and told him that the permit is ready for pick up and the work must be completed; he said he had the check ready on his desk and that he has the generator and LP tank ready to install; he said he would get going on it; I informed him that actions such as pre-citation and citations will be issued if the work isn't completed as soon as possible
|
Telephone call | | | 10/30/2002 | | DONE |
|
|
|
CALLED LEFT MESSAGE FOR JOHN,PLEASE PICK UP BY FRIDAY11-01-02
|
Plan assigned to (SAM) | 12/21/2001 | | 5/10/2002 | | DONE |
|
|
|
5/10/2002 14:30:09 SLR - activity updated through activity FIRA22 from case FIR01-00626.
|
Alarm Plan Check | 5/7/2002 | | 5/10/2002 | | PASS |
|
|
|
resubmittal of 5/7/02 acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/10/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/10/2002 | | 5/10/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/10/2002 | | DONE |
|
|
|
called john may permit ready 5-10-02 ///dld
|
Meeting | | | 5/6/2002 | | DONE |
|
|
|
Emergency generator plans resubmitted and discussed with Jim Thrasher. Based on preliminary front desk review, I gave verbal approval to allow installation work to begin without approved plans. Final field approval is not to be given until plans have been approved, permit issued and plans on site.
|
Telephone call | | | 1/3/2002 | | DONE |
|
|
|
spoke with Chris at Simplex regarding required battery calc's which they are to provided based on field measurements they are to perform. He indicates field measurements have been made and they are in process of doing calc's. I should receive them shortly.
|
Alarm Plan Check | | | 1/2/2002 | | HOLD |
|
|
|
Need battery calc's to be provided by Simplex.
|
Application received | | | 12/21/2001 | | |
|
|
|
|
Alarm Plan Check | 5/7/2002 | | | | |
|
|
|
Resubmittal received 5/7/02
|