INSP-Final Inspection | 3/4/2002 | 3/5/2002 | 3/5/2002 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled 3/5/2002 11:03:14 AM
|
DOC - Permit Finaled | 3/5/2002 | 3/5/2002 | 3/5/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/5/2002 11:03:19 AM
|
INSP-Final Inspection | 2/14/2002 | 2/15/2002 | 2/15/2002 | P | FAIL |
Troy Cobbley
|
|
|
contractor to sync strobes in areas discussed, provide flow signal from west fire sprinkler riser, post sign on FACP door. 2/15/2002 5:18:18 PM
|
Inspection Record Card- Fire | 1/23/2002 | | 1/23/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/23/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 1/23/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 1/22/2002 | | 1/22/2002 | | PASS |
|
|
|
2nd set of plans received today. Stamped and approved to issue permit.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/22/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 12/27/2001 | | 1/22/2002 | | DONE |
|
|
|
1/22/2002 17:36:59 SLR - activity updated through activity FIRA22 from case FIR01-00628.
|
Alarm Plan Check | 1/16/2002 | | 1/18/2002 | | PASS |
|
|
|
only one set of plans resubmitted. Hold for 2nd copy of plans to be received, before taking to front desk.
|
Alarm Plan Check | | | 1/16/2002 | | FAIL |
|
|
|
Called Rob at Protex 1/15/02. Rob called back 1/16 am; he will come to office to discuss review questions/comments this morning; no written review done, pending this discussion.
|
Meeting | | | 1/16/2002 | | DONE |
|
|
|
Metting with Rob Ahten. Reviewed questions and comments. Rob to make necessary corrections and re-submit later today.
|
Application received | | | 12/27/2001 | | |
|
|
|
|