INSP-Final Inspection | 5/7/2003 | 5/9/2003 | 5/9/2003 | A | PASS |
Troy Cobbley
|
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
DOC - Permit Finaled | 5/9/2003 | 5/9/2003 | 5/9/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/9/2003 11:16:35 AM
|
FIR-Aging Inspection | 12/16/2002 | 12/16/2002 | 12/16/2002 | | NR |
Troy Cobbley
|
|
|
I spoke with Viking Automatic sprinkler and they said that they will be installing the last two sprinkler heads in the canopy this week and then would be calling for an inspection 12/16/2002 9:54:42 AM
|
FIR-Aging Inspection | 12/16/2002 | 12/16/2002 | 12/16/2002 | | NR |
Troy Cobbley
|
|
|
I spoke with Viking Automatic sprinkler and they said that they will be installing the last two sprinkler heads in the canopy this week and then would be calling for an inspection 12/16/2002 9:54:42 AM
|
Telephone call | | | 2/19/2002 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY-TALKED TO RICK WILL PICKUP
|
Issue and Print Permit | | | 2/19/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/11/2002 | | 1/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 1/2/2002 | | 1/11/2002 | | DONE |
|
|
|
1/11/2002 08:59:29 JWA - activity updated through activity FIRA22 from case FIR02-00001.
|
Sprinkler Plan Check | 1/9/2002 | | 1/11/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/11/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 1/2/2002 | | 1/3/2002 | | FAIL |
Bill Alexander
|
|
|
Desing appears to be poor in regards to trapped drops (dry system). Need modification, clarification details.
|
Telephone call | | | 1/3/2002 | | DONE |
Bill Alexander
|
|
|
Called for clarifications. Indicated piping design will have trapped drops with plugs! Not accepted and need another design.
|
Application received | | | 1/2/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|