Permit NumberFIR02-00003
StatusFinaled
Name OLSON & ASSOCIATES ARCHITECTS
Site Address 3115 N SYCAMORE DR
Project NameSPR BOISE SAM VILLAGE ADDITION
Customer Number 
ePlanReview 
Description
THE BOISE SAMARITAN VILLAGE ADDITION - TO INSTALL A NEW WET AND ANIT-FREEZE SYSTEMS IN A 6,746 SQ. FT. , ONE STORY, TYPE V1HR NURSING HOME BUILDING ADDITION, SEPARATED FROM THE EXISTING STRUCTURE WITH A TWO HOUR AREA SEPARATION WALL. THIS BUILDING MUST BE FULLY FIRE SPRINKLERED FOR AREA. ALL PER RED-LINED NOTES AND ATTACHED PLAN REVIEW COMMENTS AND CONDITIONS AS REGULATED BY FIRE DEPARTMENT, WHICH COMPRISES AND BECOMES A PART OF THE APPROVED PLANS. A FIRE "INSPECTION CARD" IS REQUIRED AS A CONDITION OF THIS PERMIT, TO PROVIDE WITNESS COMPLIANCE WITH ADOPTED CODES & ORDINANCES. THIS FIRE PERMIT IS ATTACHED TO BUILDING PERMIT: BLD01-01560.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20024/23/20024/23/2002APASS
DetailsTroy Cobbley
Fire sprinkler finaled
DOC - Permit Finaled4/23/20024/23/20024/23/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 4/23/2002 11:48:45 AM
INSP-Sprinkler Rough-in/Hydro4/11/20024/12/20024/12/2002APASS
DetailsTroy Cobbley
Underground, overhead sprinkler and anti-freeze loop hydro tests OK 4/12/2002 3:52:32 PM
INSP-Supply line flush4/9/20024/10/20024/10/2002APASS
DetailsTroy Cobbley
flush on underground piping OK 4/10/2002 12:48:45 PM
INSP-Supply line flush4/9/20024/9/20024/9/2002PCANC
DetailsTroy Cobbley
canceled by contractor 4/9/2002 4:25:28 PM
INSP-Supply line flush3/14/20023/15/20023/15/2002AFAIL
DetailsTroy Cobbley
nut and bolt need to be coated before cover up 3/15/2002 12:21:08 PM
INSP-Sprinkler Rough-in/Hydro3/11/20023/12/20023/11/2002ACANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 03/11/2002 at 11:14:25. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 03/11/2002 at 14:18:36.
INSP-Sprinkler Rough-in/Hydro2/25/20022/26/20022/26/2002PFAIL
DetailsTroy Cobbley
add hangers in north rooms and in corridor 2/26/2002 5:04:43 PM
INSP-Sprinkler Rough-in/Hydro2/8/20022/8/20022/8/2002PPART
DetailsTroy Cobbley
reception hall OK for cover 2/8/2002 3:26:58 PM
INSP-Sprinkler Rough-in2/6/20022/6/20022/6/2002APART
DetailsTroy Cobbley
Added by Inspector: 430 On 2/6/2002 8:34:55 AM The front canopy attic heads to be relocated to within 6" of centerline of peak. Sunroom sprinklers OK for cover
INSP-Sprinkler Rough-in2/4/20022/5/20022/5/2002APART
DetailsTroy Cobbley
Front canopy OK for cover but approved plans not available 2/5/2002 12:34:23 PM
Inspection Record Card- Fire1/17/2002 1/17/2002 DONE
Telephone call  1/17/2002 DONE
left mess that permit is ready
Issue and Print Permit  1/17/2002 DONE
Plan assigned to (Bill)1/3/2002 1/16/2002 DONE
1/16/2002 11:16:05 SLR - activity updated through activity FIRA22 from case FIR01-00535.
Sprinkler Plan Check1/15/2002 1/16/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  1/16/2002 DONE
DetailsBill Alexander
Telephone call  1/14/2002 DONE
Received email from John Venche that riser is changing (again) and submitting new calcs. Emailed back that would not accept anymore faxes. Sending complete submittals back (2 seperate submittals of 6 each) to put together and resubmit.
Miscellaneous action  1/14/2002 DONE
gave plans back to De Best Fire Protection
Sprinkler Plan Check1/8/2002 1/14/2002 FAIL
DetailsBill Alexander
01/10/2002- Anti-freeze loop is not located down stream of alarm flow switch. Did not receive required data submittal on expansion chamber for system volumn and chamber calibration.
Telephone call  1/10/2002 DONE
DetailsBill Alexander
Faxed revised riser for attachements to the sets.
Sprinkler Plan Check1/3/2002 1/7/2002 FAIL
DetailsBill Alexander
Site location needs clarified in relation to project. Anti-freeze system incorrectly designed. Clarification of riser test connection required. No inspectors test noted. Need clarification of attic protection with section detail/s. Need piping protection tenting detail for installer/s. Need manufacturer submittals on sprinklers and expansion chamber. One head out of 6, which exceeds spacing pressure density design minimums. Obstructed construction requires clarification of obstruction as outlined in "Cover Sheet". Anti-freeze calculations do not correlate with plan piping.
Telephone call  1/7/2002 DONE
DetailsBill Alexander
Faxed copy of requirements in review this date, at 2:30pm, to Debest Fire Protection @ ###-####.
Application received  1/3/2002  
Case Summary    DONE