Case Summary | | | 9/9/2016 | | DONE |
|
|
|
|
DOC - Permit Finaled | 5/10/2002 | 5/10/2002 | 5/10/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/10/2002 4:24:40 PM
|
INSP-Final Inspection | 5/9/2002 | 5/10/2002 | 5/10/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/09/2002 at 15:18:04. Contact: ###-####.
|
Alarm Plan Check | 5/9/2002 | | 5/9/2002 | | PASS |
|
|
|
Resubmittal of a 2-hour fuel replenishment agreement received, satisfying the CONDITION for a delayed resubmittal for this information, on the previously issued plans.
|
INSP-Final Inspection | 5/2/2002 | 5/3/2002 | 5/3/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/02/2002 at 08:46:09. Contact: ###-####. need data on fuel tank reservicing to Sam; need 18 amp batteries; elevator not recalling properly and door not closing on 4th floor; 5/3/2002 4:37:24 PM
|
Alarm Plan Check | 2/20/2002 | | 2/22/2002 | | FAIL |
|
|
|
Information indicates emergency generator fuel supply is inadequate. Faxed review comments to Protex.
|
Issue permit | | | 2/8/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/7/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/7/2002 | | 2/7/2002 | | DONE |
|
|
|
|
Telephone call | | | 2/7/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (SAM) | 1/7/2002 | | 2/7/2002 | | DONE |
|
|
|
2/7/2002 14:00:07 SLR - activity updated through activity FIRA22 from case FIR02-00004.
|
Alarm Plan Check | 1/26/2002 | | 1/30/2002 | | HOLD |
|
|
|
resubmittal does not include battery calc's, indicated to be provided by Simplex.
I called Chris Willis at Simplex and he will have Stephanie fax them to me.
REsubmittal did not address several items on review re'q for resubmitttal. Called Rob Ahten, Protex, to discuss n/a, left message to call back.
|
Application received | | | 1/7/2002 | | |
|
|
|
|
Alarm Plan Check | | | 1/24/2001 | | FAIL |
|
|
|
Review Comments faxed to Protex.
|
Alarm Plan Check | 2/7/2002 | | | | PASS |
|
|
|
Plans approved with CONDITIONS for delayed resubmittal of existing FACP battery info.
|