Permit NumberFIR02-00004
StatusFinaled
Name PROTEX
Site Address 675 S 13TH ST
Project NameSHORELINE APARTMENTS
Customer Number 
ePlanReview 
Description
SHORELINE PLAZA - To install fire alarm protection within this new apartment addition, connected to the existing building fire alarm system. A new transponder control panel and notification appliance power extender unit will be added for the new addition. Coverage in the new addition will include sprinkler monitoring and partial elevator recall, audible annunciation through out the building and visual in handicapped units. Single-station, 120v, smoke detectors within the dwelling units will not be connected to the alarm system. The associated building permits are: BLD01-00011 to construct to a ground level parking garage, BLD00-808 and BLD01-00809 to construct 3 stories of apartments above the parking garage and BLD 01-02750 to modify the existing contiguous apartment structure and bring up to code per UBC Section 3402.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  9/9/2016 DONE
DOC - Permit Finaled5/10/20025/10/20025/10/2002PPASS
DetailsRick Jackson
Finaled by inspector at 5/10/2002 4:24:40 PM
INSP-Final Inspection5/9/20025/10/20025/10/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/09/2002 at 15:18:04. Contact: ###-####.
Alarm Plan Check5/9/2002 5/9/2002 PASS
Resubmittal of a 2-hour fuel replenishment agreement received, satisfying the CONDITION for a delayed resubmittal for this information, on the previously issued plans.
INSP-Final Inspection5/2/20025/3/20025/3/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/02/2002 at 08:46:09. Contact: ###-####. need data on fuel tank reservicing to Sam; need 18 amp batteries; elevator not recalling properly and door not closing on 4th floor; 5/3/2002 4:37:24 PM
Alarm Plan Check2/20/2002 2/22/2002 FAIL
Information indicates emergency generator fuel supply is inadequate. Faxed review comments to Protex.
Issue permit  2/8/2002 DONE
PLANS/APPL TAKEN TO FRONT DESK  2/7/2002 DONE
Inspection Record Card- Fire2/7/2002 2/7/2002 DONE
Telephone call  2/7/2002 DONE
left mess that permit is ready
Plan assigned to (SAM)1/7/2002 2/7/2002 DONE
2/7/2002 14:00:07 SLR - activity updated through activity FIRA22 from case FIR02-00004.
Alarm Plan Check1/26/2002 1/30/2002 HOLD
resubmittal does not include battery calc's, indicated to be provided by Simplex.
I called Chris Willis at Simplex and he will have Stephanie fax them to me.
REsubmittal did not address several items on review re'q for resubmitttal. Called Rob Ahten, Protex, to discuss n/a, left message to call back.
Application received  1/7/2002  
Alarm Plan Check  1/24/2001 FAIL
Review Comments faxed to Protex.
Alarm Plan Check2/7/2002   PASS
Plans approved with CONDITIONS for delayed resubmittal of existing FACP battery info.