INSP-Final Inspection | 11/8/2004 | 11/8/2004 | 11/8/2004 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 11/8/2004 | 11/8/2004 | 11/8/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 11/8/2004 3:10:20 PM
|
INSP-Final Inspection | 10/11/2004 | 10/11/2004 | 10/11/2004 | P | FAIL |
Rick Jackson
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Dry system under walkway trip test okay; need straps on two hangers near stair; need air gauge at dry valve 10/11/2004 1:49:57 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/6/2004 | 10/6/2004 | 10/6/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/6/2004 at 10:50:55 AM. Contact: ###-####. hydro on dry system under walkway okay 10/6/2004 12:59:01 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/4/2004 | 10/5/2004 | 10/5/2004 | A | FAIL |
Rick Jackson
|
|
|
Stop air test 43 psi Fail - air pressure at 38 psi 10/5/2004 11:44:21 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/4/2004 | 10/4/2004 | 10/4/2004 | P | DONE |
Rick Jackson
|
|
|
Start 24 hour test 12 pm with 43 psi on dry system under old walkway 10/4/2004 1:37:18 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/17/2004 | 9/17/2004 | 9/17/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/17/2004 at 8:14:52 AM. Contact: ###-####. Okay in area D and E; the temp walkway dry system is not ready and will require all tests; the walkway sprinkler system must remain in service up until the demo time 9/17/2004 11:47:29 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/15/2004 | 9/15/2004 | 9/15/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/15/2004 at 8:42:06 AM. Contact: ###-####. ^ inch main from pump room to concourse B hydro only okay 9/15/2004 2:35:24 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/10/2004 | 9/10/2004 | 9/10/2004 | P | PART |
Rick Jackson
|
|
|
Dry system for under terminal and walkway okay for hydro; 30 minutes to fill with air at 42 psi 9/10/2004 4:28:49 PM
|
INSP-Sprinkler Rough-in | 9/8/2004 | 9/8/2004 | 9/8/2004 | A | FAIL |
Rick Jackson
|
|
|
Dry system air compressor takes over 30 minutes to fill system; need to trip dry system and set air compressor to come on above low air setting 9/8/2004 11:58:33 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/3/2004 | 9/3/2004 | 9/3/2004 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/3/2004 at 10:38:54 AM. Not holding pressure (second floor at SW corner) 9/3/2004 2:19:41 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/31/2004 | 9/1/2004 | 9/1/2004 | A | PART |
Rick Jackson
|
|
|
Brian; 8:00 Hydro okay for east mechanical room, area D 1st floor and area E basement through 1st floor elevator area 9/1/2004 12:33:15 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/30/2004 | 8/31/2004 | 8/31/2004 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/30/2004 at 2:49:20 PM. Contact: ###-####. Rescheduled by inspector for 9/1 8/31/2004 3:06:37 PM
|
Plan resubmittals received | | | 8/31/2004 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2004 | 8/6/2004 | 8/6/2004 | A | PART |
Rick Jackson
|
|
|
Brian - ###-#### Hydro on west mechanical room on roof okay 8/6/2004 1:15:18 PM
|
INSP-Sprinkler Rough-in | 8/6/2004 | 8/6/2004 | 8/6/2004 | A | FAIL |
Rick Jackson
|
|
|
Overspaced in roof mechanical room at grid F/5 - G/4 and 9-10 (only area checked) 8/6/2004 10:30:29 AM
|
INSP-Sprinkler Rough-in/Hydro | 8/4/2004 | 8/5/2004 | 8/5/2004 | P | NR |
Rick Jackson
|
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Annette Moore Hydro not holding - rescheduled for 8/6 8/5/2004 2:09:39 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/27/2004 | 7/27/2004 | 7/27/2004 | A | PART |
Rick Jackson
|
|
|
Area C hydro completed 7/27/2004 2:00:37 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/23/2004 | 7/26/2004 | 7/26/2004 | P | PART |
Rick Jackson
|
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Hydro on area C okay; EQ at (3-6 inch lines) expansion joint on second level okay 7/26/2004 2:58:31 PM
|
INSP-Sprinkler Rough-in | 6/8/2004 | 6/9/2004 | 6/10/2004 | A | PART |
Rick Jackson
|
|
|
###-#### brian okay to cover rotunda only; EQ needed at area by new walkway 6/10/2004 8:53:53 AM
|
Issue and Print Permit | | | 6/8/2004 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/28/2004 | | 6/8/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/28/2004 | | 6/8/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/8/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/8/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/8/2004 | | 6/8/2004 | | DONE |
|
|
|
|
Telephone call | | | 6/8/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 5/27/2004 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 5/26/2004 | 5/26/2004 | 5/26/2004 | P | PART |
Troy Cobbley
|
|
|
Sprinkler pendants located in area "C" on the second floor west of the sky lights are ok to cover 5/26/2004 3:16:42 PM
|
INSP-Sprinkler Rough-in | 5/11/2004 | 5/12/2004 | 5/12/2004 | A | FAIL |
Rick Jackson
|
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Need EQ on 4 inch on either side of skylight as they are overspaced 5/12/2004 11:26:04 AM
|
INSP-Sprinkler Rough-in | 4/19/2004 | 4/19/2004 | 4/19/2004 | P | PART |
Rick Jackson
|
|
|
The 2.5 inch line in area D first floor has shifted from plans and branch lines installed per plans; need EQ at west end of 2.5 inch on first floor as it is overspaced from end of pipe; the tie-ins to exsisting mains aren't completed; okay on first floor area C and D - heads/drops not completed 4/19/2004 3:06:57 PM
|
Miscellaneous action | | | 2/24/2004 | | DONE |
|
|
|
Received a signed (by Dave Miller) aggreement addressing FIR02-00005-10, Items #1 and 2. Forwarded revised review notes with copy of aggreement to Greg Johnson (TVFP), attached (seperately) papers relating to FIR04-00092 (with a note).
|
Sprinkler Plan Check | 12/22/2003 | | 1/8/2004 | | PART |
Bill Alexander
|
|
|
Need sprinkler upgrading and earthquake submittals. Reference (permit/plan) attached review notes.
|
Plan assigned to (Bill) | 12/22/2003 | | 1/8/2004 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/8/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/8/2004 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/8/2004 | | DONE |
|
|
|
already pd for
|
Plan resubmittals received | | | 12/22/2003 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 6/3/2003 | 6/4/2003 | 6/4/2003 | P | PART |
Rick Jackson
|
|
|
air test on three systems //// air tests okay; will need map updated to reflect current room numbers; system not left on and operational as it is not monitored by BOI personnel 6/4/2003 2:35:39 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/3/2003 | 6/3/2003 | 6/3/2003 | P | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore started 24 hr test on three systems 6/3/2003 4:01:51 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/28/2003 | 5/28/2003 | 5/28/2003 | P | PASS |
Troy Cobbley
|
|
|
sam; Phone #: ###-#### Hydro test for dry system area "B" is ok 5/28/2003 4:00:07 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/23/2003 | 5/23/2003 | 5/23/2003 | P | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore tripped dry system to baggae handling area - trip time 1 minute; tampers and low air didn't report to fire panel; will need to reverify these signals for proper monitoring 5/23/2003 2:21:32 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2003 | 5/8/2003 | 5/8/2003 | A | PART |
Rick Jackson
|
|
|
hydro test on second floor area A and C; first floor area C; wet and preaction area B 5/8/2003 4:17:14 PM
|
Override - Parcel Holds | | | 5/7/2003 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/10/2003 | 4/11/2003 | 4/11/2003 | P | PART |
Rick Jackson
|
|
|
SAM ###-#### area A and C on third floor hydro okay 4/11/2003 3:44:29 PM
|
Override - Parcel Holds | | | 4/10/2003 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 3/24/2003 | 3/25/2003 | 3/25/2003 | A | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on first floor Area A. 3/25/2003 10:11:08 AM
|
INSP-Sprinkler Rough-in | 3/11/2003 | 3/11/2003 | 3/11/2003 | P | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Annette Moore tested pump with TVFP and Russ of Nickerson 3/11/2003 4:30:02 PM
|
INSP-Sprinkler Rough-in/Hydro | 2/13/2003 | 2/14/2003 | 2/14/2003 | P | PART |
Rick Jackson
|
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie hydro okay on basement, feed mains and header in basement; preaction for computer room; future main feeds 2/14/2003 3:19:56 PM
|
Issue permit | | | 2/13/2003 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/11/2003 | | 2/12/2003 | | PASS |
Bill Alexander
|
|
|
Temporary Concourse "A" and "B" risers and water supply connections required for the demolition of the old, and building of the new Terminal Building. (Approximately 18 months).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/12/2003 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 2/12/2003 | | DONE |
|
|
|
permit ready and fees due
|
Plan resubmittals received | | | 2/11/2003 | | |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in | 2/7/2003 | 2/7/2003 | 2/7/2003 | P | PART |
Rick Jackson
|
|
|
###-#### okay to cover area between rotunda and ticket area; need fireproofing in spots 2/7/2003 2:17:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/31/2003 | 1/31/2003 | 1/31/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 1/31/2003 at 9:26:33 AM. Contact: ###-####. will need heads in bottom of shaft on first floor' catwalk area okay 1/31/2003 3:12:22 PM
|
Sprinkler Plan Check | 1/23/2003 | | 1/29/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2003 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 1/29/2003 | | DONE |
|
|
|
PERMIT READY AND FEES DUE
|
CHANGE STATUS TO (ISS) | | | 1/29/2003 | | DONE |
|
|
|
ALREADY PD
|
Plan resubmittals received | | | 1/23/2003 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 1/10/2003 | 1/10/2003 | 1/10/2003 | A | FAIL |
Rick Jackson
|
|
|
heads below 22 inches and numerous obstructed in Area A in catwalk area for baggage handling system
|
INSP-Sprinkler Rough-in/Hydro | 12/17/2002 | 12/17/2002 | 12/17/2002 | P | PART |
Rick Jackson
|
|
|
SAM; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie antifreeze system and temp walkway areas are completed; hydro okay; tampers tested okay under FIR02-00480 12/18/2002 7:31:30 AM
|
Telephone call | | | 12/16/2002 | | DONE |
|
|
|
permit ready and fees due
|
Issue and Print Permit | | | 12/16/2002 | | DONE |
|
|
|
|
(F) Reprint permit | | | 12/16/2002 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 12/13/2002 | 12/13/2002 | 12/13/2002 | P | PART |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung hydro on temp walkway and r/i; will relocate heads at new wall as they are overspaced and at new room in temp wlakway 12/13/2002 4:06:19 PM
|
Plan resubmittals received | | | 12/13/2002 | | DONE |
Bill Alexander
|
|
|
Temporary (outside) Walkway Protection
|
Sprinkler Plan Check | 12/13/2002 | | 12/13/2002 | | PASS |
Bill Alexander
|
|
|
Temporary (outside) Walkway Protection
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/13/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 11/20/2002 | | 12/10/2002 | | FAIL |
Bill Alexander
|
|
|
Temporary Walkway plans on hold for Dave Miller's response for under walkway protection. Project on hold pending BLD review.
Dave Miller response 11/27/02 - Sprinklers required.
Approval to proceed with review: Sam Rogers, 2:00pm.
Plans denied due to lack of complete scope and fire protection requirements.
|
Telephone call | | | 12/10/2002 | | DONE |
Bill Alexander
|
|
|
Temporary Walkway denied. Faxed failed review and sent plans to front desk for calling and returning.
|
INSP-Sprinkler Rough-in/Hydro | 12/9/2002 | 12/9/2002 | 12/9/2002 | P | PART |
Rick Jackson
|
|
|
###-#### 12/10/2002 10:45:25 AM r/i for temp walkway okay; hydro okay 12/10/2002 2:41:50 PM
|
Plan resubmittals received | | | 12/4/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 12/4/2002 | | 12/4/2002 | | PASS |
Bill Alexander
|
|
|
Sky light modification of 9 sprinklers for 3rd floor Mezzanine.
|
INSP-Sprinkler Rough-in/Hydro | 12/2/2002 | 12/3/2002 | 12/3/2002 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/02/2002 at 13:21:53. Contact: ###-####. verified resubmittal on the skylight area; okay per plans; will need to verify that heads aren't painted 12/3/2002 11:35:16 AM
|
Issue permit | | | 11/27/2002 | | |
|
|
|
|
Telephone call | | | 11/27/2002 | | DONE |
|
|
|
CALLED 11-27-02
|
Sprinkler Plan Check | 11/25/2002 | | 11/26/2002 | | PASS |
Bill Alexander
|
|
|
Atrium Skylight fire sprinkler protection modification required due to obstructions. Third Floor FP2.3C.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/26/2002 | | DONE |
Bill Alexander
|
|
|
Atrium skylight modifications.
|
Plan assigned to (Bill) | 11/25/2002 | | 11/25/2002 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/25/2002 | | DONE |
|
|
|
3rd floor atrium fire sprinkler modifications.
|
Plan resubmittals received | | | 11/22/2002 | | DONE |
Bill Alexander
|
|
|
Faxed copy of 3rd floor atrium fire sprinkler modifications.
|
Sprinkler Plan Check | 11/22/2002 | | 11/22/2002 | | FAIL |
Bill Alexander
|
|
|
Fire sprinkler 3rd floor atrium modifications.
|
Telephone call | | | 11/22/2002 | | DONE |
|
|
|
Faxed failed review to Greg Johnson 2:45 pm.
|
Plan resubmittals received | | | 11/20/2002 | | DONE |
Bill Alexander
|
|
|
Revised Temporary (Sky) walkway.
|
INSP-Sprinkler Rough-in | 10/11/2002 | 10/14/2002 | 10/14/2002 | A | PART |
Rick Jackson
|
|
|
area okay in concourse A for new bathroom 10/14/2002 9:25:27 AM
|
INSP-Final Inspection | 10/10/2002 | 10/11/2002 | 10/11/2002 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/10/2002 at 13:11:25. Contact: ###-####. rescheduled for 10/14 10/11/2002 4:46:19 PM
|
INSP-Sprinkler Rough-in | 9/26/2002 | 9/26/2002 | 9/26/2002 | P | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung control valves on 1st, 2nd and 3rd floors are located above ceiling; first floor area A is located within baggage conveyor area 9/26/2002 4:12:22 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/4/2002 | 9/5/2002 | 9/5/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 09/04/2002 at 13:28:58. Contact: ###-####. heads obstructed/overspaced in basement mechanical; refer room; janitor room; EQ branch line in south room; add line and head in south room as shown on plans; heads painted in computer room; heads fire proofed in service corridor; temp walk way off concourse okay to cover; combustibles in concealed space by phone area; okay to cover mechanical chase on third floor 9/5/2002 11:05:16 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/2/2002 | 7/3/2002 | 7/3/2002 | P | FAIL |
Rick Jackson
|
|
|
SAM ###-#### heads obstructed in basement at west end mechanical; will continue r/i 7/3/2002 3:45:40 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2002 | 7/2/2002 | 7/2/2002 | A | NR |
Rick Jackson
|
|
|
SAM ###-#### Sam didn't have the latest approved a job shack; talked to Greg on phone and they will have plans for pm inspection on 7/3/02 7/2/2002 3:52:43 PM
|
| | | 7/2/2002 | | DONE |
Darla L Downs
|
|
|
Parcel Tag Notes: OKAY TO SEND OUT INSPECTIONS FOR ALL TRADES ON BLD00-03428. The following note pertains to baggage system installation.
(any questions contact John Menard at ###-####)
(5-20-02) Please override this tag for all activities associated with permit BLD02-01037. CJW Reason for OverRide:
|
| | | 7/1/2002 | | DONE |
Darla L Downs
|
|
|
Parcel Tag Notes: OKAY TO SEND OUT INSPECTIONS FOR ALL TRADES ON BLD00-03428. The following note pertains to baggage system installation.
(any questions contact John Menard at ###-####)
(5-20-02) Please override this tag for all activities associated with permit BLD02-01037. CJW Reason for OverRide:
|
Telephone call | | | 6/27/2002 | | DONE |
|
|
|
permit ready and fees due
|
Override - Parcel Holds | | | 6/27/2002 | | |
|
|
|
|
Issue permit | | | 6/27/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/12/2002 | | 6/26/2002 | | PASS |
Bill Alexander
|
|
|
Modified calculations for passenger terminal areas modified to include a 500 gpm hose demand, (not 250gpm), the abandoning of underground below area "B" (installed under building), rezoning to now include a zone #5 for entire Concourse "B". Zone #6 to feed the future Concourse "A". These plans include all changes made, i.e., walls added, preaction protection for computer room, deck changes-basement, floor zone controls, etc.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/26/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 5/20/2002 | | DONE |
|
|
|
greg ###-####
|
Override - Parcel Holds | | | 5/20/2002 | | |
|
|
|
|
Issue permit | | | 5/20/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 5/6/2002 | | 5/17/2002 | | DONE |
|
|
|
5/17/2002 14:59:55 JWA - activity updated through activity FIRA22 from case FIR02-00005.
|
Sprinkler Plan Check | 5/7/2002 | | 5/17/2002 | | PASS |
Bill Alexander
|
|
|
1.Remaining Zone # 3.
2.New addition.
3.Basement Preaction system (change).
4.Walkways.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/17/2002 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/5/2002 | | DONE |
Bill Alexander
|
|
|
|
Override - Parcel Holds | | | 4/5/2002 | | |
|
|
|
|
Issue and Print Permit | | | 4/5/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/21/2002 | | 4/4/2002 | | PASS |
Bill Alexander
|
|
|
SUBMITTAL #3 fire sprinkler package.
|
Issue and Print Permit | | | 2/26/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/14/2002 | | 2/25/2002 | | PASS |
Bill Alexander
|
|
|
Phase 2 resubmittal (1st Floor Zones 2 & 3).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/25/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 2/25/2002 | | DONE |
|
|
|
LEFT MESSAGE PERMIT READY//AIM
|
Telephone call | | | 2/12/2002 | | DONE |
|
|
|
talked to greg to verify plans are ready
|
Issue permit | | | 2/12/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/6/2002 | | 2/11/2002 | | PART |
Bill Alexander
|
|
|
Phase 2 Partial-Proceed. (1st Floor Zones 2 & 3) Plans provide appear to lack full coverage in many areas of soffited ceilings. Need verification of opening protection north and west of room 137 (first floors). Resubmittal required.
|
Miscellaneous action | | | 2/11/2002 | | DONE |
Bill Alexander
|
|
|
Took partially approved plans to front desk for calling and pickup. OK to proceed, but need approved resubmittals of stamped plans prior to inspection of this phase.
|
INSP-Sprinkler Rough-in | 1/14/2002 | 1/14/2002 | 1/14/2002 | P | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 1/14/2002 2:14:54 PM checked hangers in basement and retaining straps are installed where fireproofing is going to be applied this week.
|
Inspection Record Card- Fire | 1/11/2002 | | 1/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2002 | | DONE |
|
|
|
left mess with greg johnson that permit is ready
|
Issue permit | | | 1/11/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 1/7/2002 | | 1/10/2002 | | DONE |
|
|
|
1/10/2002 14:32:35 JWA - activity updated through activity FIRA22 from case FIR02-00005.
|
Sprinkler Plan Check | 1/7/2002 | | 1/10/2002 | | PASS |
Bill Alexander
|
|
|
(Basement Zone 2) Phase 1 submittal
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2002 | | DONE |
Bill Alexander
|
|
|
Phase 1 submittal
|
Application received | | | 1/7/2002 | | |
|
|
|
|