Permit NumberFIR02-00007
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 475 W PARKCENTER BLVD
Project NameALM-DOUBLE TREE HOTEL
Customer Number 
ePlanReview 
Description
DOUBLE TREE HOTEL - This is Phase One of an upgrade agreement dated Nov. 9, 2001 and approved by the Fire Department 11/21/0. This phase will include replacing the existing fire alarm panel with a new FAC panel and one separate transponder control unit, providing a new remote annunciator at the front entry of the building and in Office 120, reconnecting all existing initiating and annunciation devices to the new panel (compatibility has been verified by Simplex), connecting the new preaction system in the Nextel penthouse cellular phone transmission building, adding smoke detectors over the new control panels and in the cellular phone building, and adding two additional pull stations. Per the signed agreement, upgrading of existing zones, controls and notification circuits, (which includes initiating devices, elevator recall functions, monitoring of air handler smoke detection, and a/v annunciation), will not be required as part of Phase One.The associated building permit (BLD 01-01681) is for the NEXTEL CELLULAR, State- approved, 10'x20', noncombustible modular penthouse building on roof and antenna installation on roof of existing DOUBLE TREE hotel building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled2/4/20032/4/20032/4/2003PPASS
DetailsRick Jackson
Finaled by inspector at 2/4/2003 4:06:14 PM
INSP-Final Inspection3/5/20023/6/20023/6/2002APASS
DetailsRick Jackson
deliah ###-####-fn fire -re-insp
INSP-Final Inspection3/1/20023/4/20023/4/2002PFAIL
DetailsRick Jackson
need audilbe in Nextel from system alarm 3/4/2002 4:49:26 PM
INSP-Alarm Testing3/1/20023/4/20023/4/2002PFAIL
DetailsRick Jackson
###-#### need battery trouble reporting 3/4/2002 4:49:54 PM
Issue permit  2/11/2002 DONE
Inspection Record Card- Fire2/8/2002 2/8/2002 DONE
Telephone call  2/8/2002 DONE
left mess that permit is ready
Alarm Plan Check1/30/2002 2/7/2002 PASS
resubmittal adequate for approval.
PLANS/APPL TAKEN TO FRONT DESK  2/7/2002 DONE
Plan assigned to (SAM)1/7/2002 2/7/2002 DONE
2/7/2002 16:35:28 SLR - activity updated through activity FIRA22 from case FIR02-00007.
Alarm Plan Check1/23/2002 1/23/2002 FAIL
per telcon with Stephanie, Simplex, owner wants to utilize a separate releasing panel. DENIED Review comments faxed to Simplex today, with a resubmittal requirement for revised plans for proper releasing panel arrangement. CONDITIONAL APPROVAL IS GRANTED TO ALLOW FIELD INSTALLATION TO BEGIN PRIOR TO RECEIVING THE REQUIRED RESUBMITTAL. Approval to connect the Nextel preaction system will not be given until the required resubmittal has been received and approved.
Alarm Plan Check  1/18/2002 FAIL
Plans include an incorrect interconnection to release the Preaction sprinkler system in the new Nextel cellular transmission penthouse building.
Called Simplex and discussed withStephanie. She will have the designer call back to discuss this with me. Written review comments are being held, pending the call from the designer to discuss them.
Application received  1/7/2002