Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR02-00014
StatusFinaled
Name SIMPLEX
Site Address 11311 W CHINDEN BLVD
Project NameALM-HP BLDG 2 DP LAB
Customer Number 
ePlanReview 
Description
HP BLDG 2 DP LAB - To add additional duct detectors for HVAC air handler shut down and additional a/v devices within the Lab area, connected to the existing building fire alarm system.
The fire alarm application indicates there is no building permit associated with this alarm work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  7/18/2002 DONE
(F) Reprint permit  3/21/2002 DONE
INSP-Alarm Testing3/14/20023/15/20023/15/2002APASS
DetailsTroy Cobbley
fire alarm system finaled 3/14/2002 6:56:27 PM
DOC - Permit Finaled3/14/20023/14/20023/14/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 3/14/2002 6:56:39 PM
Issue permit  3/6/2002  
Plan assigned to (SAM)1/14/2002 2/21/2002 DONE
2/21/2002 14:27:56 SLR - activity updated through activity FIRA22 from case FIR02-00014.
Alarm Plan Check  2/21/2002 PASS
Acceptable per 2/6/02 resubmittal and inadditional information received 2/21/2002 from Simplex.
Telephone call  2/21/2002 DONE
Telcon With Chris at Simplex regarding battery calc's and extended power supply modules. He will fax cut sheets.
PLANS/APPL TAKEN TO FRONT DESK  2/21/2002 DONE
Inspection Record Card- Fire2/21/2002 2/21/2002 DONE
Telephone call  2/21/2002 DONE
Alarm Plan Check2/6/2002 2/19/2002 FAIL
REsubmittal information on batttery calculations and power supplies is still incorrect. Called Simplex to discuss. Hold for resolution.
Telephone call  2/18/2002 DONE
Called Stephanie at Simplex, regarding resubmittal calcs and information. Left voice message to call back.
Application received  1/14/2002  
Alarm Plan Check1/14/2002 1/14/2002 FAIL
current draw for a/v's exceeds capacityof FAC panel. Discussed with Stepahnie at Simplex who will review with HP and revise plans as necessary.