(F) Reprint permit | | | 7/18/2002 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/21/2002 | | DONE |
|
|
|
|
INSP-Alarm Testing | 3/14/2002 | 3/15/2002 | 3/15/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 3/14/2002 6:56:27 PM
|
DOC - Permit Finaled | 3/14/2002 | 3/14/2002 | 3/14/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 3/14/2002 6:56:39 PM
|
Issue permit | | | 3/6/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 1/14/2002 | | 2/21/2002 | | DONE |
|
|
|
2/21/2002 14:27:56 SLR - activity updated through activity FIRA22 from case FIR02-00014.
|
Alarm Plan Check | | | 2/21/2002 | | PASS |
|
|
|
Acceptable per 2/6/02 resubmittal and inadditional information received 2/21/2002 from Simplex.
|
Telephone call | | | 2/21/2002 | | DONE |
|
|
|
Telcon With Chris at Simplex regarding battery calc's and extended power supply modules. He will fax cut sheets.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/21/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/21/2002 | | 2/21/2002 | | DONE |
|
|
|
|
Telephone call | | | 2/21/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 2/6/2002 | | 2/19/2002 | | FAIL |
|
|
|
REsubmittal information on batttery calculations and power supplies is still incorrect. Called Simplex to discuss. Hold for resolution.
|
Telephone call | | | 2/18/2002 | | DONE |
|
|
|
Called Stephanie at Simplex, regarding resubmittal calcs and information. Left voice message to call back.
|
Application received | | | 1/14/2002 | | |
|
|
|
|
Alarm Plan Check | 1/14/2002 | | 1/14/2002 | | FAIL |
|
|
|
current draw for a/v's exceeds capacityof FAC panel. Discussed with Stepahnie at Simplex who will review with HP and revise plans as necessary.
|