Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR02-00026
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 6017 W FAIRVIEW AVE
Project NameALM-LES SCHWAB TIRES
Customer Number 
ePlanReview 
Description
LES SCHWAB TIRE CENTER - To install a new fire alarm system as required by UFC 8102.5 due to high piled storage in this existing, non-sprinklered building. The alarm system will include smoke detectors within the high piled storage areas, monitoring of 120v duct smoke detectors for HVAC air handler shutdown, monitoring of standpipe hose control valve tamper switches, audible/visual alarms, and offsite alarm monitoring.
The associated building permit (BLD 01-00460) is to add approximately 3,640 sq.ft. to the existing vehicle repair garage and modify existing CMU wall to a two hour area separation wall. The area separation wall will divide this building into two separate buildings. The east portion will be 4,140 sq.ft and the remainder building will be 15,900 sq.ft. Additional work included in this permit is to remodel the interior retail sales area and provide a one-hour occupancy separation wall between the repair garage area and the office, retail areas.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
(F) Reprint permit  7/30/2002 DONE
INSP-Final Inspection4/25/20024/26/20024/26/2002PPASS
DetailsTroy Cobbley
fire alarm finaled 4/26/2002 11:04:52 AM
DOC - Permit Finaled4/26/20024/26/20024/26/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 4/26/2002 11:05:00 AM
INSP-Final Inspection4/24/20024/25/20024/25/2002ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/24/2002 at 13:43:47. Contact: ###-####.
INSP-Final Inspection4/25/20024/25/20024/25/2002ACANC
DetailsRick Jackson
Scheduled by Inspector: 409 On 4/25/2002 12:11:13 PM
INSP-Final Inspection4/17/20024/18/20024/18/2002PFAIL
DetailsTroy Cobbley
provide racking permit for the existing tire storage racks 4/18/2002 5:07:53 PM
INSP-Final Inspection4/18/20024/18/20024/18/2002PFAIL
DetailsTroy Cobbley
provide automatic shutdown on the two existing HVAC units, test all three units and test the remaining damper
INSP-Final Inspection4/12/20024/15/20024/15/2002PFAIL
DetailsTroy Cobbley
need to test one last fire/smoke damper and all duct detectors and verify signals 4/15/2002 5:16:35 PM
Issue and Print Permit  4/2/2002 DONE
PLANS/APPL TAKEN TO FRONT DESK  3/28/2002 PASS
Plans approved with comments
Alarm Plan Check  3/28/2002 PASS
Plans approved with comments
Inspection Record Card- Fire3/28/2002 3/28/2002 DONE
Telephone call  3/28/2002 DONE
left message permit ready
Alarm Plan Check3/4/2002 3/19/2002 FAIL
Revised plans still incomplete. Conditional approval granted to begin installation prior to receiving the required resubmittal information.
Alarm Plan Check1/28/2002 2/12/2002 FAIL
Resubmittal required; review comments faxed to ADT
Application received  1/25/2002  
Plan assigned to (SAM)1/25/2002 1/25/2002 DONE
1/25/2002 10:35:36 JWA - activity updated through activity FIRA22 from case FIR02-00023.
Permit VOIDED11/4/200311/4/2003   
voided permit to old per linda hartwell