Permit Information
Permit NumberFIR02-00035
StatusFinaled
Name WESTERN FIRE PROTECTION, INC.
Site Address 1515 W STATE ST
Project NameSPR RITE AID
Customer Number 
ePlanReview 
Description
RITE AID PHARMACY DRIVE-THRU AND REMODEL To modify, add and relocate fire sprinkler protection for a pharmacy drive-thru and relocated pharmacy, new restroom and create a new 392 ft/2 store room. Occupancy is Ordinary Group 2 with spacing limits of 130 ft/2 both above and below ceilings. Construction Type is VN and the structure is fully fire sprinklered for area increase. All fire sprinkler requirements shall be per red-lined plans, attached review comments and conditions list, all as regulated by the Fire Chief, which comprises and becomes a part of the permit requirements. A fire "Inspection Card" is required as a condition of this permit, to provide witness compliance with adopted codes & ordinances. This fire permit is attached to building permit: BLD01-01403.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  10/30/2002 DONE
CALLED 10-30-02 PICK UP BY FRIDAY 11-1-02
INSP-Final Inspection8/15/20028/15/20028/15/2002PPASS
DetailsRick Jackson
DOC - Permit Finaled8/15/20028/15/20028/15/2002PPASS
DetailsRick Jackson
Finaled by inspector at 8/15/2002 1:46:35 PM
INSP-Sprinkler Rough-in/Hydro3/19/20023/19/20023/19/2002PPART
DetailsRick Jackson
Scheduled by Inspector: 409 On 3/19/2002 2:24:10 PM hydro okay 3/19/2002 2:26:17 PM
INSP-Sprinkler Rough-in2/21/20022/21/20022/21/2002PPART
DetailsRick Jackson
HARRY ###-#### okay to cover pharmacy area 2/21/2002 3:04:05 PM
Inspection Record Card- Fire2/21/2002 2/21/2002 DONE
Telephone call  2/21/2002 DONE
permit ready
Issue and Print Permit  2/21/2002 DONE
Sprinkler Plan Check2/20/2002 2/20/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/20/2002 DONE
DetailsBill Alexander
Telephone call  2/19/2002 DONE
LEFT MESS WITH NOEL THAT PLANS ARE READY
Telephone call  2/7/2002 DONE
CALLED PLANS READY
Plan assigned to (Bill)2/4/2002 2/6/2002 DONE
2/6/2002 15:57:12 JWA - activity updated through activity FIRA22 from case FIR02-00035.
Sprinkler Plan Check2/4/2002 2/6/2002 PART
DetailsBill Alexander
Need resubmittal of plans that provide more detail meeting NFPA 13 Chapter 8.
PLANS/APPL TAKEN TO FRONT DESK  2/6/2002 DONE
DetailsBill Alexander
Partial approval - to proceed, but need revised plans for inspection. Do not issue inspection card under this review/relaease!
Inspection2/5/20022/5/20022/5/2002ADONE
DetailsBill Alexander
Inspection to verify poor plans with actual construction. Contractor arrived about 10:30am and we walked through the project verifying plan submitted and project plans and construction. Plans did not match project enough to approve design (along with other problems). Specified that drive through service room must be covered and outside canopy must be of "NON-COMBUSTILBE" construction, or fire sprinklers will be required. He indicated that plywood sheeting is being installed and will meet the flame spread ate of 25 or less. I indicated that a Fire Inspector must verify it before cover.
Application received  2/4/2002  
Case Summary    DONE