Permit Information
Permit NumberFIR02-00039
StatusFinaled
Name TREASURE VALLEY BIBILE CHURCH
Site Address 12251 W USTICK RD
Project NameSPR TREASURE VBC
Customer Number 
ePlanReview 
Description
TREASURE VALLEY BIBLE CHURCH - To fully fire sprinkler a new 30,522 ft/2, one story, church with classrooms, gym and offices with a wet and dry pipe systems. Building will have a two hour area separation wall, with two types of construction. Gym and sanctuary will be Type II-1hr with remainder being Type V-1hr. Fire sprinklers are used for substitution of one-hour construction. All work is per approved plans and attachments. All fire sprinkler work shall be per red-lined notes, attached plan review comments and conditions list, which comprises and becomes a part of the approved plans, as regulated by fire department. A fire "Inspection Card" is required as a condition of this permit, to provide witness compliance with adopted codes & ordinances. This permit is attached to BLD01-02399. Associated underground supply line fire permit is: FIR01-00624 which was attached to grading permit BLD01-02392. Underground permit must be competed prior to attaching (this permit) overhead to it.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/26/20029/26/20029/26/2002PPASS
DetailsTroy Cobbley
fire sprinkler system finaled
DOC - Permit Finaled9/26/20029/26/20029/26/2002PPASS
DetailsTroy Cobbley
Finaled by inspector at 9/26/2002 2:56:21 PM
INSP-Final Inspection9/24/20029/24/20029/24/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/24/2002 at 10:45:28. Contact: ###-####. tested tampers/flows okay; need chain/lock on PIV; splash gaurd at inspectors test as shown on plans 9/24/2002 3:13:11 PM
INSP-Sprinkler Rough-in7/10/20027/10/20027/10/2002AFAIL
DetailsTroy Cobbley
All items on the correction notice for the dry system rough-in have been corrected except for protection that needs to be provided in the overbuild areas above the riser room
INSP-Sprinkler Rough-in6/7/20026/7/20026/7/2002APART
DetailsTroy Cobbley
wet system rough-in ok. Only a small section of the attic dry system was inspected. It had multiple problems so no other areas were looked at. Problems included sprinkler heads spaced too close, heads too far from deck, missing earth quake bracing and head overspaced off of a draft stop and installation of sprinklers in the hydraulic calc area not per plan. I left comment for that area to be resubmitted for Bill Alexanders approval
INSP-Sprinkler Rough-in6/4/20026/4/20026/4/2002APART
DetailsRick Jackson
Added by Inspector: 409 On 6/4/2002 10:27:15 AM okay to cover sanctuary only; fire treated plywood used
INSP-Sprinkler Rough-in5/8/20025/8/20025/8/2002APART
DetailsTroy Cobbley
Restrooms located in northwest corner of buildings ok to cover
Inspection Record Card- Fire3/22/2002 3/22/2002 DONE
Telephone call  3/22/2002 DONE
jeff
Issue and Print Permit  3/22/2002 DONE
Sprinkler Plan Check3/13/2002 3/21/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/21/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)2/7/2002 3/21/2002 DONE
DetailsBill Alexander
3/21/2002 15:26:35 JWA - activity updated through activity FIRA22 from case FIR02-00039.
Miscellaneous action  2/15/2002 DONE
Took rejected plans to front desk for calling and return.
Sprinkler Plan Check2/7/2002 2/15/2002 FAIL
DetailsBill Alexander
Many areas lack correct fire sprinkler coverage. Remote test #1, dry system attic appears to not be accurate and need reverification.
Application received  2/6/2002  
Case Summary    DONE