INSP-Final Inspection | 10/14/2002 | 10/14/2002 | 10/14/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 10/14/2002 | 10/14/2002 | 10/14/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/14/2002 10:23:12 AM
|
Plan assigned to (SAM) | 8/2/2002 | | 8/2/2002 | | DONE |
|
|
|
resubmittal
|
INSP-Alarm Testing | 7/16/2002 | 7/17/2002 | 7/17/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 7/16/2002 6:07:58 PM completed alarm testing; panel has trouble due to main board problems 7/17/2002 10:33:47 AM
|
INSP-Alarm Testing | 7/16/2002 | 7/16/2002 | 7/16/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 7/16/2002 9:49:57 AM all device testing complete and okay; av's obstructed in fan deck corridor; 7/16/2002 6:13:13 PM
|
INSP-Alarm Testing | 7/16/2002 | 7/15/2002 | 7/16/2002 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 7/16/2002 9:49:08 AM contine testing alarms; will continue on 7/16
|
INSP-Alarm Testing | 7/12/2002 | 7/12/2002 | 7/12/2002 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 7/12/2002 3:43:14 PM started to test in-duct detectors and they didn't shut down the MAU's; will continue test on 7/15
|
INSP-Alarm Testing | 7/11/2002 | 7/11/2002 | 7/11/2002 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 7/11/2002 4:35:57 PM tested pull stations and sprinkler tampers/flows; labels for some pulls need fixing; sprinklers okay
|
Issue and Print Permit | | | 6/5/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/4/2002 | | 6/4/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/4/2002 | | DONE |
|
|
|
CALLED PAUL PLANS READY 6-4-02///DLD
|
Alarm Plan Check | 6/3/2002 | | 6/3/2002 | | PASS |
Sam Rogers
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/3/2002 | | DONE |
Sam Rogers
|
|
|
|
Alarm Plan Check | 5/17/2002 | | 5/20/2002 | | PEND |
|
|
|
Resubmitttal of revised plans and specifications. No cover letter do not indicate changes; plans not couded to reflect changes. Called Paul have designers provide response to previous review comments and/or to have changes identified on plans.
|
Plan assigned to (SAM) | 2/7/2002 | | 5/14/2002 | | DONE |
|
|
|
5/14/2002 08:45:22 JWA - activity updated through activity FIRA22 from case FIR02-00130.
|
Meeting | | | 4/11/2002 | | DONE |
|
|
|
Meeting with Micron to discuss thier code research and proposed design modifications. Proposals appear correct. They will revise plans and resubmit.
|
Meeting | | | 3/19/2002 | | DONE |
|
|
|
Meeting at City offices with Matt Shipley, Mary Froemke, and Paul Marcolina to discuss design issues per UFC 51. To revise plans and resubmit.
|
Alarm Plan Check | | | 3/12/2002 | | FAIL |
|
|
|
Plans reviewed by Troy. Design issues need to be discussed; Micron to schedule a meeting with appropriate design people.
|
Application received | | | 2/7/2002 | | |
|
|
|
|