Permit Information
Permit NumberFIR02-00044
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 702 W IDAHO ST
Project NameALM-KEY BANK BUILDING
Customer Number 
ePlanReview 
Description
Key Bank Building - To replace an existing fire alarm panel and upgrade the alarm system to meet current code requirements (1997 UFC) for high rise buildings. A programmed upgrade agreement was approved 11/19/2001 by the Fire Department but the alarm plans submitted show all required upgrades are being done under this permit. The new system will include: selective coverage area smoke detection as required for high rise buildings and for door hold-open devices and elevator recall, an emergency voice alarm-signaling system, a fire department communication system, a voluntary manual alarm system, visual alarm annunciation, monitoring of sprinkler system waterflow and valve tamper and fire pump functions, duct smoke detectors for HVAC air handler shut down per UMC requirements, and duct/induct smoke detectors in return and exhaust air systems as required for high rise buildings. There is no building permit associated with this alarm work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  6/10/2004  
DOC - Permit Finaled2/24/20032/24/20032/24/2003PPASS
DetailsRick Jackson
Finaled by inspector at 2/24/2003 1:22:06 PM
INSP-Final Inspection2/24/20032/24/20032/24/2003PPASS
DetailsRick Jackson
per agreement with Dave Miller and BFD the freight elevator is not required to have elevator recall 2/24/2003 1:21:15 PM
INSP-Alarm Testing2/10/20032/13/20032/13/2003AFAIL
DetailsRick Jackson
Would Like to schedule for Thursday at 9:AM. Thanks Rick.; Phone #: ###-#### Internet Inspection Request from: Rick Groom all outstanding items corrected; awaiting letter with FD approval that the north elevator is okay without having recall; it is pre 1993 and wasn't required to have recall at time of installation 2/13/2003 3:13:46 PM
INSP-Sprinkler Rough-in/Hydro1/27/20031/30/20031/30/2003PFAIL
DetailsRick Jackson
Would like the inspection for 1pm if possible. If not please let me know.
Thanks Rick Groom Northwest Sales Co.; Phone #: ###-#### Internet Inspection Request from: Rick Groom need to verify proper air flow for duct detectors in plenum on 14th floor; need updated map reflecting initiating devices and address; need circuit breaker location at NAC panels; need label on doors for RA detectors located in restrooms as detectors are concealed; retest fire phones for 9-14 floors; need to test elevator recall 1/31/2003 7:59:38 AM
FIR-Aging Inspection12/27/200212/27/20021/3/2003 PART
DetailsRick Jackson
Talked to Dave Maxwell and he said they will schedule for next week for testing 1/3/2003 8:59:12 AM
Issue permit  5/6/2002 DONE
Inspection Record Card- Fire5/2/2002 5/2/2002 DONE
Telephone call  5/2/2002 DONE
permit ready
PLANS/APPL TAKEN TO FRONT DESK  5/1/2002 PASS
Plan assigned to (SAM)2/11/2002 5/1/2002 DONE
5/1/2002 16:39:16 SLR - activity updated through activity FIRA22 from case FIR02-00044.
Alarm Plan Check4/12/2002 4/30/2002 PASS
Resubmittal approved.
Alarm Plan Check  2/25/2002 FAIL
Phoned NW Sales to discuss questions essential to enable further review.
Application received  2/11/2002