INSP-Final Inspection | 5/14/2002 | 5/14/2002 | 5/14/2002 | A | PASS |
Troy Cobbley
|
|
|
TJ Maxx part of system OK
|
DOC - Permit Finaled | 5/14/2002 | 5/14/2002 | 5/14/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/14/2002 7:39:42 AM
|
INSP-Alarm Testing | 5/8/2002 | 5/9/2002 | 5/9/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide missing esch. for sprinkler pendants, remove dead bolt on south exit door, mount fire extinguishers at 48", provide signage for fire extinguishers, relocate knox box, provide building address 5/10/2002 8:47:20 AM
|
Inspection Record Card- Fire | 4/11/2002 | | 4/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 4/11/2002 | | DONE |
|
|
|
permit ready
|
Issue and Print Permit | | | 4/11/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 3/27/2002 | | 4/10/2002 | | PASS |
|
|
|
approved with numerous CONDITIONS. A 3rd review fee applies.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/10/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/12/2002 | | 4/10/2002 | | DONE |
|
|
|
4/10/2002 10:37:30 SLR - activity updated through activity FIRA22 from case FIR02-00048.
|
Alarm Plan Check | 3/14/2002 | | 3/14/2002 | | FAIL |
|
|
|
Resubmittal does not include plans for the Best Buy store as required on the original review notes. No further review done.
|
Alarm Plan Check | | | 2/22/2002 | | FAIL |
|
|
|
Plans inlcude only the TJ Max area; all areas of the building shall be included. Comments discussed by phone with Jason Minnic and faxed to AEI.
|
Application received | | | 2/12/2002 | | |
|
|
|
|