INSP-Alarm Testing | 3/12/2002 | 3/13/2002 | 3/13/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/12/2002 at 14:52:32. Contact: ###-####. Found two horn/strobes within this project T-tapped. One was the new strobe in the bathroom and the other one on the adjacent wall. Fixed by Mike Kroll and tested. Installed per plans. Installer of T-tapped devices was "Danny". 3/13/2002 10:29:13 AM
|
INSP-Final Inspection | 3/12/2002 | 3/13/2002 | 3/13/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/12/2002 at 14:54:57. Contact: ###-####.
|
DOC - Permit Finaled | 3/13/2002 | 3/13/2002 | 3/13/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 3/13/2002 10:30:10 AM
|
Inspection Record Card- Fire | 3/8/2002 | | 3/8/2002 | | DONE |
|
|
|
|
Telephone call | | | 3/8/2002 | | DONE |
|
|
|
|
Issue permit | | | 3/8/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/20/2002 | | 3/7/2002 | | DONE |
|
|
|
3/7/2002 18:26:56 SLR - activity updated through activity FIRA22 from case FIR02-00059.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/7/2002 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/5/2002 | | FAIL |
|
|
|
The address and building name on application and plan do not match the address and buidling name for the associated buidling permit number, although the described work seems to correlate.
Faxed notice to Alarmco to rectify the discrepancy.
|
Application received | | | 2/20/2002 | | |
|
|
|
|
Alarm Plan Check | 3/7/2002 | | 3/7/2001 | | PASS |
|
|
|
Resubmittal of 3/7 adequate.
|
Alarm Plan Check | | | 3/6/2001 | | FAIL |
|
|
|
Battery calc's are incorrect. Discussed with Alan at Alarmco; he will resubmit revised calc's. Review not faxed.
|