Permit Information
Permit NumberFIR02-00059
StatusFinaled
Name ALARMCO
Site Address 1276 E RIVER STREET Unit: 201
Project NameALM-RIVER PLAZA-2ND FLR
Customer Number 
ePlanReview 
Description
ROAD TO RECOVERY / RIVER PLAZA - To add a horn/strobe in an accessible restroom, which is being remodeled, connected to the existing building alarm system. Alarm devices in the other portions of this tenant space #201, were previously approved under FIR 01-00335. Also to revise the wiring to the duct detectors for smoke dampers and HVAC shut down.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Alarm Testing3/12/20023/13/20023/13/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 03/12/2002 at 14:52:32. Contact: ###-####. Found two horn/strobes within this project T-tapped. One was the new strobe in the bathroom and the other one on the adjacent wall. Fixed by Mike Kroll and tested. Installed per plans. Installer of T-tapped devices was "Danny". 3/13/2002 10:29:13 AM
INSP-Final Inspection3/12/20023/13/20023/13/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 03/12/2002 at 14:54:57. Contact: ###-####.
DOC - Permit Finaled3/13/20023/13/20023/13/2002APASS
DetailsRick Jackson
Finaled by inspector at 3/13/2002 10:30:10 AM
Inspection Record Card- Fire3/8/2002 3/8/2002 DONE
Telephone call  3/8/2002 DONE
Issue permit  3/8/2002 DONE
Plan assigned to (SAM)2/20/2002 3/7/2002 DONE
3/7/2002 18:26:56 SLR - activity updated through activity FIRA22 from case FIR02-00059.
PLANS/APPL TAKEN TO FRONT DESK  3/7/2002 DONE
Alarm Plan Check  3/5/2002 FAIL
The address and building name on application and plan do not match the address and buidling name for the associated buidling permit number, although the described work seems to correlate.
Faxed notice to Alarmco to rectify the discrepancy.
Application received  2/20/2002  
Alarm Plan Check3/7/2002 3/7/2001 PASS
Resubmittal of 3/7 adequate.
Alarm Plan Check  3/6/2001 FAIL
Battery calc's are incorrect. Discussed with Alan at Alarmco; he will resubmit revised calc's. Review not faxed.