Permit Information
Permit NumberFIR02-00060
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 2285 S APPLE ST
Project NameSPR WALGREENS
Customer Number 
ePlanReview 
Description
WALGREENS STORE #6971 - To install an approved NFPA 13 system per UFC 1003 in a new 14,420 ft/2 single story, Type VN, retail building, with drive-up pharmacy. Grading under own permit BLD01-02251. Underground fire permit attached to grading permit: FIR01-00605. Fire sprinklers used for area increase. The fire sprinkler system shall comply with NFPA 13-1999, submitted and approved red-lined plans with attached review comment and conditions list, as regulated by the Fire Chief. A fire "Inspection Card" is required as a condition of this permit, to provide witness of compliance with the same. This permit is attached to BLD02-02240.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/21/20025/22/20025/22/2002APASS
DetailsRick Jackson
Scheduled by Inspector: 409 On 5/21/2002 4:11:45 PM
DOC - Permit Finaled5/22/20025/22/20025/22/2002APASS
DetailsRick Jackson
Finaled by inspector at 5/22/2002 9:14:39 AM
INSP-Sprinkler Rough-in/Hydro5/2/20025/2/20025/2/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 5/2/2002 12:16:36 PM hydro on overhead and underground okay; need to test alarms
INSP-Supply line flush5/1/20025/1/20025/1/2002PPASS
DetailsTroy Cobbley
underground flush OK
INSP-Sprinkler Rough-in4/24/20024/24/20024/24/2002APART
DetailsRick Jackson
Added by Inspector: 409 On 4/24/2002 9:02:45 AM one strap by pharmacy; anti freeze loop not complete
Issue permit  3/5/2002 DONE
Inspection Record Card- Fire3/4/2002 3/4/2002 DONE
Telephone call  3/4/2002 DONE
###-####
PLANS/APPL TAKEN TO FRONT DESK  3/4/2002 DONE
DetailsBill Alexander
Plan assigned to (Bill)2/20/2002 3/4/2002 DONE
3/4/2002 14:44:21 JWA - activity updated through activity FIRA22 from case FIR02-00060.
Sprinkler Plan Check3/1/2002 3/4/2002 PART
DetailsBill Alexander
Requires resubmittal on earthquake calcs and outside control valve (required).
Sprinkler Plan Check2/20/2002 2/28/2002 FAIL
DetailsBill Alexander
Sprinkler applications are not correct. Heads using are not OR and thus not listed for reduced area allowance for lower ceiling heights. Drive-Thru is not Light Hazard Occupancy, but OH-1.
Miscellaneous action  2/28/2002 DONE
Took failed package to front desk for calling and returning to Debest Fire.
Application received  2/20/2002  
Case Summary    DONE