Plan resubmittals received | | | 11/21/2002 | | DONE |
|
|
|
Bill A.
|
INSP-Sprinkler Rough-in/Hydro | 8/9/2002 | 8/12/2002 | 8/12/2002 | A | PASS |
Troy Cobbley
|
|
|
hydro test for the overhead system is OK. Permit also finaled 8/12/2002 4:42:47 PM
|
DOC - Permit Finaled | 8/12/2002 | 8/12/2002 | 8/12/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 8/12/2002 4:42:52 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/8/2002 | 8/9/2002 | 8/9/2002 | A | FAIL |
Troy Cobbley
|
|
|
above ground hydro test failed 8/9/2002 2:11:09 PM
|
INSP-Supply line flush | 8/8/2002 | 8/8/2002 | 8/8/2002 | P | PASS |
Troy Cobbley
|
|
|
flush OK
|
INSP-Sprinkler Rough-in | 7/17/2002 | 7/17/2002 | 7/17/2002 | A | PASS |
Troy Cobbley
|
|
|
Underground thrust block ok for cover
|
INSP-Sprinkler Rough-in/Hydro | 7/11/2002 | 7/11/2002 | 7/11/2002 | A | PASS |
Troy Cobbley
|
|
|
Underground supply OK to cover
|
INSP-Supply line flush | 7/11/2002 | 7/11/2002 | 7/11/2002 | P | CANC |
Troy Cobbley
|
|
|
duplicate inspection 7/11/2002 3:24:25 PM
|
INSP-Supply line flush | 6/27/2002 | 6/28/2002 | 6/28/2002 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the stub out only. The thrust blocking and beding is OK but the nuts and bolts need the non corrosive covering. Contractor said it would be taken care of monday 6/28/2002 2:56:37 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2002 | 6/28/2002 | 6/27/2002 | A | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 06/27/2002 at 13:26:24. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 06/27/2002 at 13:27:22.
|
INSP-Sprinkler Rough-in | 5/13/2002 | 5/14/2002 | 5/14/2002 | P | PART |
Rick Jackson
|
|
|
r/i- ###-####- bruce Modules A-B-C okay; plans kept in Tom's office; all areas above finsihed ceiling are sheetrocked 5/14/2002 4:03:04 PM
|
Issue and Print Permit | | | 5/13/2002 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 2/21/2002 | | 3/11/2002 | | DONE |
|
|
|
3/11/2002 15:08:11 JWA - activity updated through activity FIRA22 from case FIR02-00061.
|
Sprinkler Plan Check | 3/7/2002 | | 3/11/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/11/2002 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/11/2002 | | 3/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 3/11/2002 | | DONE |
|
|
|
SPOKE WITH JOHN WARNICK PERMIT READY
|
Miscellaneous action | | | 3/1/2002 | | DONE |
|
|
|
Packages taken to front desk for calling and returning.
|
Application received | | | 2/21/2002 | | |
|
|
|
|
Sprinkler Plan Check | 2/21/2002 | | | | FAIL |
Bill Alexander
|
|
|
Requires forward flow test piping, PVC exposed, Hydrant exceeds limit to FDC, Water supply certificate taken off wrong address, etc.
|
Case Summary | | | | | DONE |
|
|
|
|