Case Summary | | | 6/21/2004 | | |
|
|
|
|
INSP-Final Inspection | 9/25/2002 | 9/26/2002 | 9/26/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 9/26/2002 10:44:50 AM
|
DOC - Permit Finaled | 9/26/2002 | 9/26/2002 | 9/26/2002 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 9/26/2002 10:44:55 AM
|
INSP-Final Inspection | 9/24/2002 | 9/24/2002 | 9/24/2002 | P | FAIL |
Rick Jackson
|
|
|
tested detectors for AHU shutsown - larger units have 30 second delay; need to trim back flange on weatherproof covers so the detector cover can be removed; need NFPA record of completion 9/24/2002 3:21:50 PM
|
INSP-Final Inspection | 9/18/2002 | 9/23/2002 | 9/23/2002 | P | FAIL |
Troy Cobbley
|
|
|
relocate the electric alarm bell to the fdc location, provide a dedicated non switched circuit for the air compressor, provide enclosures for the duct detectors. Test the dry pipe system for signals. 9/23/2002 3:31:47 PM 9/23/2002 3:37:39 PM
|
Issue permit | | | 7/24/2002 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 3/1/2002 | | 7/18/2002 | | DONE |
|
|
|
7/18/2002 10:35:54 430 - activity updated through activity FIRA22 from case FIR02-00070.
|
Alarm Plan Check | 7/18/2002 | | 7/18/2002 | | PASS |
Sam Rogers
|
|
|
Plans approved with conditions
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/18/2002 | | DONE |
Sam Rogers
|
|
|
|
Inspection Record Card- Fire | 7/18/2002 | | 7/18/2002 | | DONE |
|
|
|
|
Telephone call | | | 7/18/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 5/21/2002 | | 6/10/2002 | | FAIL |
|
|
|
Plans held for review by SLR upon his return form vacation, due to lack of a/v devices.
Plans failed for to lack of a/v devices. Revised review faxed to Protex.
|
Alarm Plan Check | | | 3/13/2002 | | FAIL |
|
|
|
Review comments faxed to Protex
|
Application received | | | 3/1/2002 | | |
|
|
|
|