Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR02-00070
StatusFinaled
Name TREASURE VALLEY BIBILE CHURCH
Site Address 12251 W USTICK RD
Project NameTREASURE VALLEY BIBLE CHURCH
Customer Number 
ePlanReview 
Description
TREASURE VALLEY BIBLE CHURCH - To install a new fire alarm system in a new building. Plans for the alarm system include monitoring of the fire sprinkler system, induct smoke detectors for release of fire/smoke dampers, duct detectors for HVAC air handler shut down, area smoke detectors for release of fire/smoke door hold open devices, voice evacuation system in the Santuary , exit corridors and in the Chapel area which are A2.1 occupancies. The Gymnasium, which is also an A2.1, is to remain unfinished and unoccupied and will not be provided with voice evacuation until a separate fire alarm permit has been issued. One inside audible alarm with a manual pull station will be provided in the B occupancy portion of the building.
The associated building permit (BLD 01-02399) is to construct a new 30,522 sq. ft. one story, fully fire sprinklered church with classrooms, gym and offices. Building will have a two hour area separation wall with two types of construction. Gym and sanctuary will be Type II?1hr with remainder being Type V?1hr. Fire sprinklers shall be used for substitution of one?hour construction. One hour exit passageways shall be provided on each side of the sanctuary for the side exits.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  6/21/2004  
INSP-Final Inspection9/25/20029/26/20029/26/2002APASS
DetailsTroy Cobbley
fire alarm finaled 9/26/2002 10:44:50 AM
DOC - Permit Finaled9/26/20029/26/20029/26/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 9/26/2002 10:44:55 AM
INSP-Final Inspection9/24/20029/24/20029/24/2002PFAIL
DetailsRick Jackson
tested detectors for AHU shutsown - larger units have 30 second delay; need to trim back flange on weatherproof covers so the detector cover can be removed; need NFPA record of completion 9/24/2002 3:21:50 PM
INSP-Final Inspection9/18/20029/23/20029/23/2002PFAIL
DetailsTroy Cobbley
relocate the electric alarm bell to the fdc location, provide a dedicated non switched circuit for the air compressor, provide enclosures for the duct detectors. Test the dry pipe system for signals. 9/23/2002 3:31:47 PM 9/23/2002 3:37:39 PM
Issue permit  7/24/2002 DONE
Plan assigned to (SAM)3/1/2002 7/18/2002 DONE
7/18/2002 10:35:54 430 - activity updated through activity FIRA22 from case FIR02-00070.
Alarm Plan Check7/18/2002 7/18/2002 PASS
DetailsSam Rogers
Plans approved with conditions
PLANS/APPL TAKEN TO FRONT DESK  7/18/2002 DONE
DetailsSam Rogers
Inspection Record Card- Fire7/18/2002 7/18/2002 DONE
Telephone call  7/18/2002 DONE
Alarm Plan Check5/21/2002 6/10/2002 FAIL
Plans held for review by SLR upon his return form vacation, due to lack of a/v devices.
Plans failed for to lack of a/v devices. Revised review faxed to Protex.
Alarm Plan Check  3/13/2002 FAIL
Review comments faxed to Protex
Application received  3/1/2002