Permit Information
Permit NumberFIR02-00071
StatusFinaled
Name PROTEX
Site Address 1199 W SHORELINE LN Unit: 308
Project NameALM-FOREST RIVER #1
Customer Number 
ePlanReview 
Description
FOREST RIVER #1 - To install a new fire alarm system in an existing building. The system will include supervision of the fire sprinkler system, duct detectors for HVAC monitoring, selective coverage smoke detectors for elevator recall, and offsite alarm monitoring. The associated building permit (BLD 99-01122) is still open and is to remodel 2 existing office suites on the 3rd floor, to make into one tenant space totaling 1,572 sq.ft. Work is to include demolishing part of an interior wall to create an 8' opening and part of the entry/corridor wall area, construction of some new interior walls for closets, relocation of entry/corridor door, construct a small one hour fire rated wall section at entry/corridor wall, new fire rated window next to entry door, interior finish, minor suspended ceiling work, possible minor fire sprinkler relocation work, mechanical, and electrical work.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/9/20046/9/20046/9/2004APASS
DetailsRick Jackson
DOC - Permit Finaled6/9/20046/9/20046/9/2004APASS
DetailsRick Jackson
Finaled by inspector at 6/9/2004 11:07:35 AM
INSP-Final Inspection7/31/20038/4/20038/4/2003PCANC
DetailsRick Jackson
sorry about the 1st inspection ; Phone #: ###-#### Internet Inspection Request from: Terry Owsley per Rob - this will be rescheduled 8/4/2003 3:30:19 PM
INSP-Final Inspection7/31/20038/1/20037/31/2003PCANC
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection9/27/20029/27/20029/27/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/27/2002 at 08:09:35. Contact: ###-####. tested primary and alternate recall for elevator; elevator machine room smoke detector doesn't recall to any floor - needs recall 9/27/2002 3:53:47 PM
INSP-Final Inspection7/23/20027/23/20027/23/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/23/2002 at 07:40:56. Contact: ###-####. alternate floor recall for elevator not provided; need approval from Dave Miller; told Grant of Prtoex to have owner submit to Dave Miller for approval/disapproval of current situation 7/23/2002 3:21:32 PM
INSP-Final Inspection6/19/20026/20/20026/20/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 6/19/2002 10:43:31 AM elevator has primary recall and no shunt; map at annunciator; zones defined at panel; keys for knox box 6/20/2002 10:00:57 AM
INSP-Final Inspection6/18/20026/19/20026/19/2002ACANC
DetailsRick Jackson
Scheduled by Inspector: 409 On 6/18/2002 12:24:57 PM ###-####
INSP-Final Inspection6/18/20026/18/20026/18/2002PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 06/18/2002 at 07:32:49. Contact: ###-####.
Issue and Print Permit  6/4/2002 DONE
Telephone call  5/23/2002 DONE
left mess that permit is ready
Alarm Plan Check5/22/2002 5/22/2002 PASS
Resubmittal received 5/21 and 5/22 now acceptable.
PLANS/APPL TAKEN TO FRONT DESK  5/22/2002  
Plan assigned to (SAM)3/1/2002 5/22/2002 DONE
5/22/2002 14:09:40 SLR - activity updated through activity FIRA22 from case FIR02-00071.
Alarm Plan Check4/9/2002 4/22/2002 FAIL
Resubmittal still not correct; does not properly address items in origial review. Revised review comments faxed to Protex.
Alarm Plan Check  3/11/2002 FAIL
Review comments faxed to Protex 3/11/02
Application received  3/1/2002  
Inspection Record Card- Fire5/23/2002