INSP-Final Inspection | 6/20/2002 | 6/21/2002 | 6/21/2002 | P | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 6/21/2002 1:28:16 PM
|
DOC - Permit Finaled | 6/21/2002 | 6/21/2002 | 6/21/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 6/21/2002 1:28:22 PM
|
INSP-Final Inspection | 6/18/2002 | 6/19/2002 | 6/19/2002 | P | FAIL |
Troy Cobbley
|
|
|
all devices need to be tested, heat detectors need to be relocated or the vents blocked, provide 50 ah batteries for the main facp, provide approved hardware on doors, provide updated map 6/19/2002 1:03:15 PM
|
Issue permit | | | 4/8/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 3/5/2002 | | 3/22/2002 | | DONE |
|
|
|
3/22/2002 09:10:35 SLR - activity updated through activity FIRA22 from case FIR02-00073.
|
Alarm Plan Check | | | 3/22/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/22/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/22/2002 | | 3/22/2002 | | DONE |
|
|
|
|
Telephone call | | | 3/22/2002 | | DONE |
|
|
|
permit ready
|
Application received | | | 3/5/2002 | | |
|
|
|
|