INSP-Final Inspection | 8/6/2002 | 8/7/2002 | 8/7/2002 | P | PASS |
Rick Jackson
|
|
|
MIKE ###-####
|
DOC - Permit Finaled | 8/7/2002 | 8/7/2002 | 8/7/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/7/2002 2:40:13 PM
|
INSP-Final Inspection | 7/31/2002 | 8/1/2002 | 8/1/2002 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/31/2002 at 11:20:22. Contact: ###-####. alarms not pretested by contractor 8/1/2002 9:05:34 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/15/2002 | 7/17/2002 | 7/17/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/15/2002 at 11:35:54. Contact: ###-####. hydro okay on all systems 7/17/2002 12:52:21 PM
|
INSP-Supply line flush | 4/18/2002 | 4/19/2002 | 4/19/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/18/2002 at 13:44:28. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 4/16/2002 | 4/16/2002 | 4/16/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/16/2002 at 10:15:56. Contact: ###-####. okay to cover; dry sidewalls not complete they will leave this area uncovered; heads due in this week 4/16/2002 3:59:30 PM
|
INSP-Sprinkler Rough-in | 4/12/2002 | 4/12/2002 | 4/12/2002 | P | FAIL |
Rick Jackson
|
|
|
Scott ###-#### soffits in kitchen/dining area are over 8 inches and will need pendants; laundry room soffits with heads too close to soffit; verify temp of furnace rooms may rewuire higher temp heads; draft stops require fire stopping; dry system not complete; need to complete wet system dry sidewall heads 4/12/2002 4:04:52 PM
|
Inspection Record Card- Fire | 4/12/2002 | | 4/12/2002 | | DONE |
|
|
|
|
Telephone call | | | 4/12/2002 | | DONE |
|
|
|
permit ready
|
Issue permit | | | 4/12/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/10/2002 | | 4/11/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/11/2002 | | DONE |
Bill Alexander
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2002 | 4/9/2002 | 4/9/2002 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/08/2002 at 09:43:48. Contact: ###-####. per Bill - no inspections on overhead; underground approved for install and overhead requires resubmittal 4/9/2002 11:00:38 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/3/2002 | 4/5/2002 | 4/5/2002 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/03/2002 at 16:42:17. Contact: ###-####. talked to Trent and he said they would be ready next week 4/5/2002 2:46:29 PM
|
INSP-Supply line flush | 4/3/2002 | 4/4/2002 | 4/4/2002 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/03/2002 at 16:41:31. Contact: ###-####. underground cover only - okay 4/4/2002 8:31:29 AM
|
Plan assigned to (Bill) | 3/7/2002 | | 4/3/2002 | | DONE |
|
|
|
4/3/2002 08:40:57 JWA - activity updated through activity FIRA22 from case FIR02-00081.
|
Sprinkler Plan Check | 3/22/2002 | | 4/3/2002 | | PART |
Bill Alexander
|
|
|
Requires resubmittal to correlate calculation with plans!
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/3/2002 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 4/3/2002 | | 4/3/2002 | | DONE |
|
|
|
|
Telephone call | | | 4/3/2002 | | DONE |
|
|
|
called bob
|
Issue permit | | | 4/3/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/22/2002 | | 4/1/2002 | | PART |
Bill Alexander
|
|
|
Underground permitted and released only at this time.
|
Sprinkler Plan Check | 3/7/2002 | | 3/14/2002 | | FAIL |
Bill Alexander
|
|
|
Fire sprinkler coverage is lacking in this facility. Outside stairs require full protection. The outside decks will be require fire protection. Fire department connection exceeds the maximum allowance. Need some data submittals.
|
Miscellaneous action | | | 3/14/2002 | | DONE |
Bill Alexander
|
|
|
Took plans to front desk for calling and returning.
|
Application received | | | 3/7/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|