Permit Information
Permit NumberFIR02-00082
StatusFinaled
Name SIMPLEX/GRINNELL FIRE PROTECTION
Site Address 501 E MYRTLE ST
Project NameSPR IDAHO HOUSING & FINANCE
Customer Number 
ePlanReview 
Description
IDAHO HOUSING & FINANCE-PARK PLACE BLDG* To tap into an existing 3" fire sprinkler main and install a new Single Interlock Preaction System within an 440 ft/2 computer room. This building is fully fire sprinklered. All fire sprinkler work shall comply with NFPA 13-1999, the red-lined plans, attached review comment and conditions list, as enforced by the Fire Chief. A fire "Inspection Card" is required as a condition of this permit, to provide witness of compliance with the same. This permit is not attached to any building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/24/20026/24/20026/24/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 6/24/2002 2:22:31 PM
DOC - Permit Finaled6/24/20026/24/20026/24/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 6/24/2002 2:23:30 PM
INSP-Alarm Testing6/3/20026/11/20026/6/2002ACANC
DetailsRick Jackson
MICK ###-#### Disp set to [CANC] by a contractor via Hello! on 06/06/2002 at 13:45:33.
Issue permit  4/18/2002  
Telephone call  4/8/2002 DONE
left mess that permit is ready
Sprinkler Plan Check3/25/2002 4/8/2002 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/8/2002 DONE
DetailsBill Alexander
Issue and Print Permit  3/19/2002 DONE
Sprinkler Plan Check3/13/2002 3/18/2002 PART
DetailsBill Alexander
A. OH-1 hose demand should be 250 and not 100 gpm? (Reference 7-2.3.1.1)
B. Actual sprinkler area density exceeds the same as calculated? (Reference 8-4.4.3.1)
C. Return bend fitting are shorted in the calculations? (Reference 8-4.4.5(a)
D. Include/add node points on the riser section, that correlate with calculation input. (Reference 8-1.1.1(34)
E.Piping on the plan starting at node 8 does not correlate with calcs? (Reference 8-1.1.1(34)
F. Provide information on how this added system will be drained. (8-1.1.1, UFC 1001.3)
G. No information was provided for electric activation operation of this fire suppression system. Is the detection/releasing/monitoring panel a "Reliable" or another brand. No data provided other than electrical by others? If another brand, it must be listed and compatible. This releasing panel must be connected to an existing alarm panel.
H. The Reliable Supertrol submittal data indicates a "Non-Supervised" System. Page 2 item "B" would indicate a supervised system. Explain how this system verbifies the integrity of this systems piping, and provide data.
PLANS/APPL TAKEN TO FRONT DESK  3/18/2002 DONE
DetailsBill Alexander
Requires resubmittal prior to inspections.
Plan assigned to (Bill)3/7/2002 3/18/2002 DONE
3/18/2002 16:38:47 JWA - activity updated through activity FIRA22 from case FIR02-00082.
Sprinkler Plan Check3/7/2002 3/11/2002 FAIL
DetailsBill Alexander
Lack elevation and riser detail to verify calculations. Room system protection is designed for Light Hazard and occupancy is Ordinary Group 1. No sprinkler head data submitted.
Telephone call  3/11/2002 DONE
Tom Easton called and we conversed over the lacking information and under design of the submittal. He will submit new plans, including sprinkler head data.
Telephone call  3/8/2002 DONE
Called Tom Easton @ Grinnell 3:15 pm, (not in), to verify room identfication (occupancy hazard classification) protecting. Covering an energen system area? Need to know if this is replacing it or in conjuction with it? Existing riser detail was conveniently omitted from plan?
Application received  3/7/2002  
Case Summary    DONE
Inspection Record Card- Fire4/8/2002