INSP-Final Inspection | 5/29/2002 | 5/29/2002 | 5/29/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 5/29/2002 7:37:20 AM
|
DOC - Permit Finaled | 5/29/2002 | 5/29/2002 | 5/29/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 5/29/2002 8:08:39 AM
|
INSP-Final Inspection | 5/21/2002 | 5/22/2002 | 5/22/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 5/21/2002 4:12:26 PM phone line problems; map at FACP and remote LED for pharmacy AHU 5/22/2002 9:15:22 AM
|
Issue permit | | | 5/2/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 4/29/2002 | | 4/29/2002 | | PASS |
|
|
|
Received revised plans and cut sheets changing SD to a compatible model.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/29/2002 | | |
|
|
|
|
Plan assigned to (SAM) | 3/15/2002 | | 4/22/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 4/5/2002 | | 4/22/2002 | | HOLD |
|
|
|
Resubmittal acceptable, except for lack of verification of compatibility of ESL self-diagnostic smoke detector with the Fire Lite panel. AEI to call mfg'r tomorrow to request a comptability sheet and fax to me.
|
Alarm Plan Check | | | 3/29/2002 | | FAIL |
|
|
|
Plan review comments discussed with and faxed to Jason at AEI. Incomplete manual alarm system shown.
|
Application received | | | 3/15/2002 | | |
|
|
|
|