Permit Information
Permit NumberFIR02-00096
StatusFinaled
Name PROTEX
Site Address 332 W HALE ST
Project NameBROOKSIDE APARTMENTS
Customer Number 
ePlanReview 
Description
BROOKSIDE APARTMENTS - To install fire alarm systems in each apartment building of this complex, connected to a single FAC panel for offsite communication. The alarm systems will include sprinkler monitoring, manual pull stations and audible alarm annunciation in each dwelling unit, with a/v annunciation provided in hearing impaired dwelling units . A separate Fire Alarm permit is issued to correspond with the building permit issued for each building. The associated building permits are to construct new, sprinklered, three-story, wood framed, apartment buildings. Each building has a separate building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20028/29/20028/29/2002PPASS
DetailsRick Jackson
DOC - Permit Finaled8/29/20028/29/20028/29/2002PPASS
DetailsRick Jackson
Finaled by inspector at 8/29/2002 3:47:26 PM
Inspection Record Card- Fire7/17/2002 7/17/2002 DONE
Issue and Print Permit  7/17/2002 DONE
Alarm Plan Check7/12/2002 7/16/2002 PASS
Resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  7/16/2002 DONE
Telephone call  7/2/2002 DONE
Telcon from Rob Ahten, Protex. Discussed and explained each comments on my 7/1/02 review. Rob understands and will resubmit with revisions per review comments.
Alarm Plan Check6/24/2002 7/1/2002 FAIL
Revised plans are incomplete and do not address all the required items specified in the previous plans review. Faxed review comments to Protex and to Alpine Electric.
Telephone call  6/11/2002 DONE
need to come and pick up not approved.
Alarm Plan Check4/16/2002 4/16/2002 FAIL
Front counter review of resubmittal walk-in by Dave Sheridan, Alpine Electric. Plans do not show same FAC panels as the cut sheets/interconnection diagram from mfgr; no details on the panel interconnections and sprinkler "supervisory" functions; battery calc's still using 24 hrs instead of 60; sprinkler devices to be supervised are not properly shown, questionable wiring lengths in Vd calc's; all items were specified in original written review. Dave Sheridan is taking plans to Protex for revision and resubmittal.
Alarm Plan Check  4/5/2002 FAIL
Review comments faxed to Alpine Electric and discussed with Dave Sheridan Alpine Electric and Jack at Newport Alarm.
Application received  3/19/2002