INSP-Final Inspection | 8/29/2002 | 8/29/2002 | 8/29/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 8/29/2002 | 8/29/2002 | 8/29/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 8/29/2002 3:47:26 PM
|
Inspection Record Card- Fire | 7/17/2002 | | 7/17/2002 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/17/2002 | | DONE |
|
|
|
|
Alarm Plan Check | 7/12/2002 | | 7/16/2002 | | PASS |
|
|
|
Resubmittal acceptable.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/16/2002 | | DONE |
|
|
|
|
Telephone call | | | 7/2/2002 | | DONE |
|
|
|
Telcon from Rob Ahten, Protex. Discussed and explained each comments on my 7/1/02 review. Rob understands and will resubmit with revisions per review comments.
|
Alarm Plan Check | 6/24/2002 | | 7/1/2002 | | FAIL |
|
|
|
Revised plans are incomplete and do not address all the required items specified in the previous plans review. Faxed review comments to Protex and to Alpine Electric.
|
Telephone call | | | 6/11/2002 | | DONE |
|
|
|
need to come and pick up not approved.
|
Alarm Plan Check | 4/16/2002 | | 4/16/2002 | | FAIL |
|
|
|
Front counter review of resubmittal walk-in by Dave Sheridan, Alpine Electric. Plans do not show same FAC panels as the cut sheets/interconnection diagram from mfgr; no details on the panel interconnections and sprinkler "supervisory" functions; battery calc's still using 24 hrs instead of 60; sprinkler devices to be supervised are not properly shown, questionable wiring lengths in Vd calc's; all items were specified in original written review. Dave Sheridan is taking plans to Protex for revision and resubmittal.
|
Alarm Plan Check | | | 4/5/2002 | | FAIL |
|
|
|
Review comments faxed to Alpine Electric and discussed with Dave Sheridan Alpine Electric and Jack at Newport Alarm.
|
Application received | | | 3/19/2002 | | |
|
|
|
|