Permit Information
Permit NumberFIR02-00098
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 8000 S FEDERAL WAY
Project NameSPR MICRON MASK SHOP FIRE LINE
Customer Number 
ePlanReview 
Description
MICRON MASK SHOP-UG FIRE SERVICE LINES * To install a new 200' of 8" C-900, and Ductile Iron fire service supply main into the Micron Mask Shop. Also included is the installation of approximately 185' of 4" C-900 and FDC connection piping, pit (access). All related work shall be in accordance with UFC-1997, NFPA 24-1995 and NFPA 13-1999 as regulated by the Fire Chief. No other related site utilities are included in this permit. No OH piping is allowed under this permit. This permit is attached to GRADING PERMIT BLD01-02143. Mask Shop Shell Permit is BLD01-02222.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/3/20027/3/20027/3/2002APASS
DetailsRick Jackson
Added by Inspector: 409 On 7/3/2002 8:25:16 AM
DOC - Permit Finaled7/3/20027/3/20027/3/2002APASS
DetailsRick Jackson
Finaled by inspector at 7/3/2002 8:26:05 AM
INSP-Supply line flush5/16/20025/16/20025/16/2002PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/16/2002 at 09:07:30. Contact: ###-####. underground hydro okay for FDC and supply main 5/16/2002 2:01:09 PM
INSP-Supply line flush4/25/20024/26/20024/26/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/25/2002 at 11:28:10. Contact: ###-####. supply line flush okay 4/26/2002 11:21:31 AM
Issue permit  4/9/2002 DONE
Inspection Record Card- Fire4/8/2002 4/8/2002 DONE
Telephone call  4/8/2002 DONE
called shawn plans ready 4-8-02 ///dld
Plan assigned to (Bill)3/19/2002 4/8/2002 DONE
4/8/2002 09:47:50 JWA - activity updated through activity FIRA22 from case FIR02-00098.
Sprinkler Plan Check3/22/2002 4/8/2002 PASS
DetailsBill Alexander
UG Permit only from point of fire line connection to 6" above floor.
PLANS/APPL TAKEN TO FRONT DESK  4/8/2002 DONE
DetailsBill Alexander
Miscellaneous action  3/22/2002 DONE
Doing this work prior to obtaining a permit! Left note with permit approval for front desk to double fee this permit.
Sprinkler Plan Check3/19/2002 3/19/2002 FAIL
DetailsBill Alexander
Plan submitted lack: 1. Required detail for installation requirements. a. Testing requirements. b. Flushing requirements. c. Bury depth. d. Thrust protection. d. Piping and installation requirements for FDC. etc. 2. No permit application provided with submittals.
03/24/2002 - Above submittal was for the grading (utilities) permit updates/changes and not fire sprinkler submitals!
Application received  3/19/2002  
Case Summary    DONE