INSP-Final Inspection | 7/3/2002 | 7/3/2002 | 7/3/2002 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 7/3/2002 8:25:16 AM
|
DOC - Permit Finaled | 7/3/2002 | 7/3/2002 | 7/3/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 7/3/2002 8:26:05 AM
|
INSP-Supply line flush | 5/16/2002 | 5/16/2002 | 5/16/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/16/2002 at 09:07:30. Contact: ###-####. underground hydro okay for FDC and supply main 5/16/2002 2:01:09 PM
|
INSP-Supply line flush | 4/25/2002 | 4/26/2002 | 4/26/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/25/2002 at 11:28:10. Contact: ###-####. supply line flush okay 4/26/2002 11:21:31 AM
|
Issue permit | | | 4/9/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/8/2002 | | 4/8/2002 | | DONE |
|
|
|
|
Telephone call | | | 4/8/2002 | | DONE |
|
|
|
called shawn plans ready 4-8-02 ///dld
|
Plan assigned to (Bill) | 3/19/2002 | | 4/8/2002 | | DONE |
|
|
|
4/8/2002 09:47:50 JWA - activity updated through activity FIRA22 from case FIR02-00098.
|
Sprinkler Plan Check | 3/22/2002 | | 4/8/2002 | | PASS |
Bill Alexander
|
|
|
UG Permit only from point of fire line connection to 6" above floor.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/8/2002 | | DONE |
Bill Alexander
|
|
|
|
Miscellaneous action | | | 3/22/2002 | | DONE |
|
|
|
Doing this work prior to obtaining a permit! Left note with permit approval for front desk to double fee this permit.
|
Sprinkler Plan Check | 3/19/2002 | | 3/19/2002 | | FAIL |
Bill Alexander
|
|
|
Plan submitted lack: 1. Required detail for installation requirements. a. Testing requirements. b. Flushing requirements. c. Bury depth. d. Thrust protection. d. Piping and installation requirements for FDC. etc. 2. No permit application provided with submittals.
03/24/2002 - Above submittal was for the grading (utilities) permit updates/changes and not fire sprinkler submitals!
|
Application received | | | 3/19/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|