Permit Information
Permit NumberFIR02-00124
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 5440 W FRANKLIN RD
Project NameALM-SUNDANCE BUSINESS CENTER
Customer Number 
ePlanReview 
Description
SUNDANCE BUSINESS CENTER - To install a new fire alarm system in an existing sprinklered building. The system will provide offsite sprinkler monitoring. There is no associated building permit shown on application.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/24/20025/28/20025/28/2002AFAIL
DetailsRick Jackson
SHAUN ###-#### need compatibility for smoke detector and Record of Completion 5/28/2002 10:19:13 AM
INSP-Final Inspection5/28/20025/28/20025/28/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 5/28/2002 4:00:19 PM received compatibility and record of completion
DOC - Permit Finaled5/28/20025/28/20025/28/2002PPASS
DetailsRick Jackson
Finaled by inspector at 5/28/2002 4:00:29 PM
Plan assigned to (SAM)4/1/2002 5/9/2002 DONE
5/9/2002 10:25:19 SLR - activity updated through activity FIRA22 from case FIR02-00124.
Alarm Plan Check5/7/2002 5/9/2002 PASS
resubmittal of 5/7 acceptable.
PLANS/APPL TAKEN TO FRONT DESK  5/9/2002 DONE
Inspection Record Card- Fire5/9/2002 5/9/2002 DONE
Telephone call  5/9/2002 DONE
CALLED LEFT V-MESSAGE 5-9-02///DLD
Issue and Print Permit  5/9/2002 DONE
Alarm Plan Check  5/6/2002 FAIL
Did not provide required battery details specified in previous review. Faxed revised review comments to Fire Sentry.
Alarm Plan Check  4/18/2002 FAIL
Resubmitted plans 4/4/02 -Plan review faxed to Fire Sentry.
Application received  4/1/2002  
Inspection Record Card- Fire4/1/2002 4/1/2002 DONE
Alarm Plan Check4/1/2002 4/1/2002 FAIL
Plans reviewed at front desk. Inadequate; plans taken back by contractor for revision and resubmission.