INSP-Final Inspection | 10/14/2002 | 10/14/2002 | 10/14/2002 | P | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 10/14/2002 | 10/14/2002 | 10/14/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/14/2002 10:23:07 AM
|
INSP-Final Inspection | 10/4/2002 | 10/7/2002 | 10/7/2002 | A | PART |
Rick Jackson
|
|
|
to mainly review cleanroom walls and protection under ducts. Jonathon Lee foreman on site; Phone #: ###-#### Internet Inspection Request from: Trent Bice okay per plans; need info on work in corridor used for tool wipe down area; EQ on main riser to wall 10/7/2002 3:04:05 PM
|
INSP-Final Inspection | 10/4/2002 | 10/4/2002 | 10/4/2002 | A | CANC |
Rick Jackson
|
|
|
Jonathon lee foreman on site. Clean room and fan attic.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
|
INSP-Sprinkler Rough-in/Hydro | 7/3/2002 | 7/8/2002 | 7/8/2002 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/03/2002 at 14:10:20. Contact: ###-####.cancel per chris
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2002 | 7/8/2002 | 7/8/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/08/2002 at 10:04:03. Contact: ###-####. all systems hydro okay 7/8/2002 4:51:04 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/26/2002 | 6/27/2002 | 6/27/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/26/2002 at 15:38:54. Contact: ###-####. all deficiencies corrected; awaiting heads for drops to hydro all systems and test alarms 6/27/2002 5:00:18 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/26/2002 | 6/26/2002 | 6/26/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/26/2002 at 10:04:09. Contact: ###-####. all items corrected from previous inspections; need to sprinkler above corridor in sub fab area 6/27/2002 7:00:48 AM
|
Issue and Print Permit | | | 6/26/2002 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 6/24/2002 | 6/25/2002 | 6/25/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/24/2002 at 14:54:55. Contact: ###-####. eq on main feed and FDC; need walls at AHU in basement 6/25/2002 4:33:54 PM
|
Sprinkler Plan Check | 6/20/2002 | | 6/25/2002 | | PASS |
Bill Alexander
|
|
|
Field changes and with calculations.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/25/2002 | | PASS |
Bill Alexander
|
|
|
Field changes and revised calculations.
|
INSP-Sprinkler Rough-in/Hydro | 6/24/2002 | 6/24/2002 | 6/24/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/24/2002 at 08:09:43. Contact: ###-####. straps; hangers and several obstructions 6/25/2002 7:06:36 AM
|
INSP-Sprinkler Rough-in/Hydro | 6/19/2002 | 6/21/2002 | 6/21/2002 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/19/2002 at 16:33:59. Contact: ###-####. I ran out of time today; will reschedule for 6/24 6/21/2002 4:02:38 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/18/2002 | 6/19/2002 | 6/19/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/18/2002 at 16:33:28. Contact: ###-####. hangers in office area; clean has modifications to plans - need to resubmit with clacs for review and approval; will continue inspection on 6/20 6/19/2002 4:02:29 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/17/2002 | 6/18/2002 | 6/18/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/17/2002 at 16:56:27. Contact: ###-####. met with Mike; will need resubmittals for clean room 6/18/2002 4:52:27 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/13/2002 | 6/14/2002 | 6/14/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/13/2002 at 08:18:42. Contact: ###-####. received call from Mike of Shilo and he said he wouldn't be there and he would reschedule for next week; went to job trailer and reviewed plans; left c/n with Les about having provisions to test flow switches in gas rooms 6/14/2002 3:49:18 PM
|
Inspection Record Card- Fire | 6/11/2002 | | 6/11/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/11/2002 | | DONE |
|
|
|
###-####
|
Issue permit | | | 6/11/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/10/2002 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 6/7/2002 | | 6/10/2002 | | PASS |
Bill Alexander
|
|
|
Received sprinkler head analysis reports and incorproating them in City Plans only.
|
Telephone call | | | 6/3/2002 | | DONE |
Bill Alexander
|
|
|
Recieved phone call from Bob Knight, Shilo questioning my request for more information. Made comment that Boise requires information surpassing anywhere else.
My response was basically - provide the information requested.
He said he would comply.
|
Sprinkler Plan Check | 6/1/2002 | | 6/3/2002 | | PART |
Bill Alexander
|
|
|
Modified water supply information-revised calculations throughout all areas verified.
Remote calculations densities do not match design cover sheets with remote test #1, deficient with 3 heads. Others are questioned since the calculations provided are difficult to interpret due to lack of final head analysis (number/identified heads operating, elevation of heads operating, specified head k-factor, minimum operating pressures/flows each).
Faxed letter.
|
Telephone call | | | 5/15/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 5/15/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/14/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 4/5/2002 | | 5/14/2002 | | DONE |
|
|
|
5/14/2002 08:45:22 JWA - activity updated through activity FIRA22 from case FIR02-00130.
|
Sprinkler Plan Check | 4/29/2002 | | 5/14/2002 | | PART |
Bill Alexander
|
|
|
05/09/2002 - Received modified plans that are legible.
05/14/2002 - Approved to proceed, but requires resubmittal of items (reference review notes). Double fees apply for working without a permit.
|
Meeting | | | 5/8/2002 | | DONE |
Bill Alexander
|
|
|
Micron (Paul Marciolina) GC-Representative and Shilo (Bob Knight and field superintendant) requested meeting to see what the dificulty was concerning plans.
Plans were designed by an outside firm and Shilo indicated they followed the same design under Microns instructions. Shilo indicated that they were told these plans were previously reviewed and approved by me (per Jerry O'Neil)? Micron denied this after a phone call verifying comments made by Shilo. Micron disagreed and said Shilo was not.
I asked for plans that I can read building lines for romm identification boundaries, etc.
Shilo and Micron wanted permission to start prior to appoved plans. I reiterated that a signed letter of compliance would be accepted (with consent to comply with any code violations at there own expense). They aggreed.
Meeting basically dismissed.
|
Sprinkler Plan Check | 4/5/2002 | | 4/19/2002 | | FAIL |
Bill Alexander
|
|
|
Basement problems with calculations (area/density) and head spacing on the plans. Some areas (appear) to lack protection. Plans do not provide more detail/information. Need to get anf provide "the basics" prior to further reviewing of plans.
|
Telephone call | | | 4/19/2002 | | DONE |
|
|
|
12:00 PM: called Shawn Fenneran and asked for a meeting to go over the plans. He siad he could not today, but would send a "Runner". I interated that once he got the plans, call (me) and we shall review my denial and requests. (The "basic" code issue of design with area/density requirements)
|
Application received | | | 4/5/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|