INSP-Final Inspection | 7/26/2002 | 7/26/2002 | 7/26/2002 | A | PASS |
Rick Jackson
|
|
|
|
DOC - Permit Finaled | 7/26/2002 | 7/26/2002 | 7/26/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 7/26/2002 9:41:22 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/11/2002 | 7/11/2002 | 7/11/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 7/11/2002 10:58:57 AM hydro on UG and overhead okay 7/11/2002 1:01:05 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2002 | 5/9/2002 | 5/9/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/07/2002 at 14:36:59. Contact: ###-####. okay to cover 5/9/2002 1:32:35 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/3/2002 | 5/6/2002 | 5/6/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/03/2002 at 10:12:58. Contact: ###-####. head not installed in closet; attic heads not installed; straps needed throughout 5/6/2002 11:29:24 AM
|
Telephone call | | | 5/1/2002 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Issue and Print Permit | | | 5/1/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/25/2002 | | 5/1/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2002 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 4/5/2002 | | 4/26/2002 | | DONE |
|
|
|
4/26/2002 11:45:17 JWA - activity updated through activity FIRA22 from case FIR02-00131.
|
Meeting | | | 4/18/2002 | | DONE |
|
|
|
Met with Don Weland and Bob Knight on this project and discussed items listed in the failed activity review. 9:30 AM.
|
Sprinkler Plan Check | 4/5/2002 | | 4/17/2002 | | FAIL |
Bill Alexander
|
|
|
Lacking all elevation pressure loss in the attic sprinkler protection calculations. Lack proper coverage due to missing draft stops, skylight/soffits in the attic and incorrect use of attic head. Questions on shower stall. Questioned coverage on opening from ground floor to 3rd floor roof next to inside stairs. Need to calculate the most demanding single head demand on the 3rd floor.
|
Telephone call | | | 4/17/2002 | | DONE |
|
|
|
Called Don Weland (Shilo-Designer) and illustrated problems with attic system and had enough to deny plans. Continueing with wet system.
|
Application received | | | 4/5/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/1/2002 | | | | |
|
|
|
|