INSP-Final Inspection | 2/22/2010 | 2/22/2010 | 2/22/2010 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit final approved.
|
FIR-Aging Inspection | 12/3/2009 | 12/3/2009 | 12/7/2009 | P | DONE |
Forrest France
|
|
|
Okay for permit final
|
INSP-Final Inspection | 8/19/2004 | 8/25/2004 | 8/25/2004 | P | FAIL |
Rick Jackson
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Tampers/air/flow tested okay; sprinkler systems overdue annual inspection - last inspection Feb 2003 8/25/2004 1:34:09 PM
|
Case Summary | | | 7/20/2004 | | DONE |
|
|
|
|
Miscellaneous action | | | 7/15/2004 | | DONE |
|
|
|
Emailed John Venche regarding getting this permit finaled by verifying Hi/Low air and alarm switch operation. (The alarm permit has been finaled).
|
INSP-Sprinkler Rough-in/Hydro | 5/12/2004 | 5/18/2004 | 5/18/2004 | A | NR |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Talked to Jim and he was not able to get the alarm company at the building but will reschedule when he can get all parties together to get the trip test done 5/18/2004 1:27:29 PM
|
INSP-Final Inspection | 5/12/2004 | 5/13/2004 | 5/12/2004 | P | CANC |
Rick Jackson
|
|
|
Contact: Jim; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
Miscellaneous action | | | 5/5/2004 | | DONE |
|
|
|
Emailed John Venche to finish the job or get back to me within 5 working days.
|
Miscellaneous action | | | 6/3/2003 | | DONE |
Bill Alexander
|
|
|
Emailed John Venche to verify a check valve on the system and get this permit finaled. Attached a copy of the review notes.
|
INSP-Final Inspection | 5/22/2002 | 5/23/2002 | 5/23/2002 | A | FAIL |
Rick Jackson
|
|
|
fn george- ###-#### need fire alarm plans for all new devices; ball valve for alarm switch to be supervised; will have to trip test after fire plans have been approved and installed 5/23/2002 9:59:33 AM
|
INSP-Sprinkler Rough-in/Hydro | 5/23/2002 | 5/23/2002 | 5/23/2002 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 5/23/2002 9:56:21 AM hydro and r/i okay
|
Inspection Record Card- Fire | 5/23/2002 | | 5/23/2002 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/22/2002 | | 5/22/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/5/2002 | | 4/22/2002 | | PART |
Bill Alexander
|
|
|
Plans lack information.
1. Backflow prevention device not shown, calculated or verified.
2. Calculations provided from another street, not associated with the system street tapped.
3. System/s main drain are not shown or verified to be piped to the outside or recepticle of a size and capacity to take the require full flow drain tests.
4. Lack submittal data on Dry Pipe Valve.
|
Telephone call | | | 4/22/2002 | | DONE |
|
|
|
CALLED JOHN PERMIT READY 4-22-02 ///DLD
|
Issue and Print Permit | | | 4/22/2002 | | DONE |
|
|
|
|
Application received | | | 4/5/2002 | | |
|
|
|
|
Plan assigned to (Bill) | 4/5/2002 | | | | |
|
|
|
|