Permit Information
Permit NumberFIR02-00152
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 3085 N COLE RD
Project NameSPR EVERGREEN PLAZA CANOPY
Customer Number 
ePlanReview 
Description
(EVERGREEN PLAZA-JOANN FABRICS CANOPY/WALKWAY - PHASE 3) Fire sprinkler the entry walkway and canopies above JoAnn Fabrics on east wall. This building is fully sprinklered for allowable area increase. The fire sprinkler system shall comply with NFPA 13-1999, red-lined plans, attached review comment and conditions list; as regulated by the Fire Chief. An approved and stamped plan, permit and fire "Inspection Card" is required on site as a condition of this permit, to provide witness of compliance to this work. This permit is attached to BLD02-00425.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20035/9/20035/9/2003APASS
DetailsTroy Cobbley
DOC - Permit Finaled5/9/20035/9/20035/9/2003APASS
DetailsTroy Cobbley
Finaled by inspector at 5/9/2003 11:16:47 AM
INSP-Sprinkler Rough-in7/2/20027/3/20027/3/2002PPASS
DetailsTroy Cobbley
rough-in for canopy is OK. Ok for cover 7/3/2002 3:19:06 PM
INSP-Sprinkler Rough-in/Hydro7/2/20027/2/20027/2/2002AFAIL
DetailsTroy Cobbley
hangers over the tax office still need to be relocated. Hydro test for the dry system is OK 7/2/2002 2:20:43 PM 7/2/2002 2:21:02 PM
INSP-Sprinkler Rough-in/Hydro6/27/20026/28/20026/28/2002AFAIL
DetailsTroy Cobbley
hydro test failed. Repair leaks, remove wire from the pipe, alin upright head in attic space with the deck slope, attach hangers and longitudinal EQ braces to the top chord of trusses instead of the bottom chord, retest system and reinspect 6/28/2002 11:22:05 AM
Issue and Print Permit  5/21/2002 DONE
Sprinkler Plan Check5/2/2002 5/15/2002 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/15/2002 DONE
DetailsBill Alexander
Inspection Record Card- Fire5/15/2002 5/15/2002 DONE
Telephone call  5/15/2002 DONE
SPOKE WITH RAY PERMIT READY AND FEES DUE
Telephone call  4/24/2002 DONE
plans denied will pick up
Sprinkler Plan Check4/15/2002 4/23/2002 FAIL
DetailsBill Alexander
1. Lack head spacing for UBC required draft stops.
2. Lack dry system total capacity (phase 1, 2, and this phase 3).
3. Dry pendants exceed spacing verified (120 ft/2).
4. Plans and calculations do not correlate.
Miscellaneous action  4/23/2002 DONE
DetailsBill Alexander
Took plans and calculations (4 sets) to front counter for returning to contractor
Application received  4/15/2002  
Case Summary    DONE