INSP-Final Inspection | 5/9/2003 | 5/9/2003 | 5/9/2003 | A | PASS |
Troy Cobbley
|
|
|
|
DOC - Permit Finaled | 5/9/2003 | 5/9/2003 | 5/9/2003 | A | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 5/9/2003 11:16:47 AM
|
INSP-Sprinkler Rough-in | 7/2/2002 | 7/3/2002 | 7/3/2002 | P | PASS |
Troy Cobbley
|
|
|
rough-in for canopy is OK. Ok for cover 7/3/2002 3:19:06 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/2/2002 | 7/2/2002 | 7/2/2002 | A | FAIL |
Troy Cobbley
|
|
|
hangers over the tax office still need to be relocated. Hydro test for the dry system is OK 7/2/2002 2:20:43 PM 7/2/2002 2:21:02 PM
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2002 | 6/28/2002 | 6/28/2002 | A | FAIL |
Troy Cobbley
|
|
|
hydro test failed. Repair leaks, remove wire from the pipe, alin upright head in attic space with the deck slope, attach hangers and longitudinal EQ braces to the top chord of trusses instead of the bottom chord, retest system and reinspect 6/28/2002 11:22:05 AM
|
Issue and Print Permit | | | 5/21/2002 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/2/2002 | | 5/15/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/15/2002 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 5/15/2002 | | 5/15/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/15/2002 | | DONE |
|
|
|
SPOKE WITH RAY PERMIT READY AND FEES DUE
|
Telephone call | | | 4/24/2002 | | DONE |
|
|
|
plans denied will pick up
|
Sprinkler Plan Check | 4/15/2002 | | 4/23/2002 | | FAIL |
Bill Alexander
|
|
|
1. Lack head spacing for UBC required draft stops.
2. Lack dry system total capacity (phase 1, 2, and this phase 3).
3. Dry pendants exceed spacing verified (120 ft/2).
4. Plans and calculations do not correlate.
|
Miscellaneous action | | | 4/23/2002 | | DONE |
Bill Alexander
|
|
|
Took plans and calculations (4 sets) to front counter for returning to contractor
|
Application received | | | 4/15/2002 | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|